FRIEDLAND PA4 Installation & Operating Manual Download Page 17

INST

ALLA

TION

6. Ensure the Mains Adaptor is disconnected at the

Control Panel.  Remove the appropriate Zone wire

link and then connect the wires to the Control Panel

terminals as shown in the diagrams on pages 13 - 15.

7. When the wiring has been completed, re-connect

the Mains Adaptor.

8. Wait 4 minutes for any PIR Movement Detectors to

stabilise, and then clear all protected area(s).

9. No Zone or 24 Hr LEDs should be ‘ON’ at the

Control Panel at this stage.

TESTING MAGNETIC CONTACTS AT
THE CONTROL PANEL

1. First, ensure that all doors and windows fitted with

Magnetic Contacts are closed.

2. Press         and the ‘Clear’ LED will illuminate

Note:  At this stage, if any Magnetic Contacts are

open or PIR Movement Detectors are activated,

the relevant Zone LED(s) will be illuminated and

the panel will beep,  The number of beeps will

indicate which Zone is open.  You should ensure

that no movement occurs in areas fitted with PIR

Movement Detectors, as this may cause

confusion during the test sequence.  If walking

past a PIR Movement Detector is unavoidable,

allow 10 seconds at the Control Panel for the PIR

Movement Detector to settle.

3. Open the first contact, the Control Panel will emit a

number of beeps corresponding to the Zone

number the detector is connected to and the

relevant Zone LED will flash.  

Close the contact to silence the beeps and

extinguish the LED.

4. Repeat the test sequence for all Magnetic

Contacts fitted.

5. When the Magnetic Contacts have been tested

successfully, press       to return to the Standby

Mode.

6. Now disconnect the Mains Adaptor before

continuing with the installation.

INSTALLING THE
EXTERNAL SIREN

The External Siren should be fitted to the outside of

the building in a prominent position that is clearly

visible and at a height that is relatively inaccessible

to an intruder. 

Consideration should also be given to the cable

route to the siren, with the cable preferably passing

directly through the external wall into the back of

the siren housing.

FITTING THE EXTERNAL SIREN UNIT

IMPORTANT:  If ladders are required to reach the

mounting position of the Siren they should be

positioned on a firm stable surface at the correct

angle and suitably secured before use.

1. Undo the two front cover retaining screws and

remove the front cover by sliding up and away

from the backplate.

2. Fix the siren mounting bracket to the backplate

using the M3 screws, nuts and washers supplied.

3. Run the required length of cable from the Control

Panel to the External Siren position.  Drill a

suitable hole through the wall so that the cable

enters through the rear of the housing without

showing on the outside of the property.

PA4 Alarm

15

BACK-PLATE

CABLE
ENTRY

HOLE

SIREN

BRACKET

SIREN

SIREN 

COVER

AWAY

RESET

Summary of Contents for PA4

Page 1: ...ave premises by entry exit route ENTRY 1 Enter premises by entry exit route 2 Enter your 4 digit password If a mistake is made re enter the correct passcode MAINS CLEAR 24Hr Zone 1 Zone 2 Zone 3 Zone...

Page 2: ...requirements differ from area to area therefore we recommend that you contact your Local Borough Environmental Officer to obtain full details of your area s requirements SAFETY WARNINGS Before procee...

Page 3: ...11 Testing the PIR Movement Detectors at the Control Panel 11 Page No TYPICAL WIRING ARRANGEMENTS 12 INSTALLING THE MAGNETIC CONTACT DETECTORS Wiring the Magnetic Contacts 14 Testing Magnetic Contacts...

Page 4: ...n alarm signal at the Control Panel if the system is armed PIR detectors will also detect animals so ensure that pets are not permitted access to areas fitted with PIR Movement Detectors when the syst...

Page 5: ...nd a higher level of security where required Important The PA4 system can be expanded to contain maximum of 7 PIR detectors Component Order Code Accessory Pack comprising the following 2 x Passive Inf...

Page 6: ...1 Other Detectors can be connected to Zones 2 3 and 4 to protect the remaining areas within the property as required 24 HOUR TAMPER CIRCUIT Many system components incorporate tamper protection facili...

Page 7: ...ation The program Alarm Duration time is 20 minutes however this can be set to between 01 20 minutes depending on individual requirements Note Most Local Authority noise pollution requirements set lim...

Page 8: ...Contact Detectors are suitable for mounting in dry interior locations only Decide which doors and windows are to be protected by fitting the Magnetic Contact Detectors Normally the front and back doo...

Page 9: ...ccupants remain in the household make sure that any detectors which are to be omitted are wired exclusively to those Zone s Remember that a Walk Through Zone cannot also be selected on the Home settin...

Page 10: ...he Control Panel drill 3 x 6mm holes and insert the 30mm plastic wall plugs supplied Using the 30mm No 8 screws fix the Control Panel loosely onto the two slotted holes at the top The top screws may b...

Page 11: ...ply to each PIR Movement Detector Black 0V ve supply to each PIR Movement Detector Yellow Normally closed detector contact alarm Blue Zone circuit Green 24 Hr normally closed Tamper Circuit White The...

Page 12: ...ft of the PCB Important Do not touch the PIR sensor in the middle of the PCB as any marking may impair the unit s performance If accidentally touched clean with a lint free cloth 3 The unit can be mou...

Page 13: ...5 7 When the wiring has been completed connect the plug in Mains Adaptor Wait 4 minutes for the detectors to stabilise Only the Mains LED should be ON at the Control Panel Note If any Zone or 24 Hr LE...

Page 14: ...18 D BELL B 21 22 AUX CONTROL PANEL PIR MOVEMENT DETECTOR WHITE Wiring diagram for a Single PIR Detector on a zone Wiring diagram for two PIR Detectors to a single zone with all cables returning to t...

Page 15: ...hour connections from multiple detectors PIR MOVEMENT DETECTOR N C 24 Hr BLUE YELLOW GREEN WHITE 3 4 Z 2 1 2 Z1 5 6 Z3 7 8 Z4 11 12 24Hr 13 14 SPEAKER 17 18 D BELL B 21 22 AUX CONTROL PANEL RED BLACK...

Page 16: ...ct Switch housing 2 Carefully remove the outer sheath of the cable and then strip 5mm of insulation from the Yellow and Blue wires Connect the Yellow and Blue wires to the Contact Switch terminals as...

Page 17: ...the relevant Zone LED will flash Close the contact to silence the beeps and extinguish the LED 4 Repeat the test sequence for all Magnetic Contacts fitted 5 When the Magnetic Contacts have been tested...

Page 18: ...r the Mains Adaptor to appear warm to the touch when in use Note Ensure that the adaptor will not be removed from the socket or accidently switched off when the system is in use Optional Back up Batte...

Page 19: ...to indicate that the system is now in the Installer Programming Mode Once programming is complete press to return to Standby Mode Note When selecting options the system will allow 30 seconds to make a...

Page 20: ...e selected Zones This feature is useful if you have a regular requirement to arm the system with a permanent selection Zone s omitted For example at night when you may wish to have the detectors on th...

Reviews: