![FRIEDHELM LOH RITTAL DK 7030.950 Assembly And Operating Instructions Manual Download Page 12](http://html1.mh-extra.com/html/friedhelm-loh/rittal-dk-7030-950/rittal-dk-7030-950_assembly-and-operating-instructions-manual_2332680012.webp)
12
Rittal LED light strip
6 Operation
EN
◾ Ensure that the following settings are activated for
the individual parameters in the "Details" group box.
Parameter
Setting
Enable
Active
Name
Task 1
Description
RED Vandalism
Delay
0
Delay Mode
Switch on Delay
Action
Set Variable Value
Tab. 3:
Settings in the "Task Configuration – Details" dialogue
◾ Click the
Setup
button
The "Configure Set Variable Value" dialogue appears.
Fig. 6:
"Configure Set Variable Value" dialogue
◾ Ensure that the following settings are activated for
the individual parameters.
Parameter
Setting
Device
CMCIII-IO3
Variable
Output 1.Relay
Value on True
On
Value on False
Off
Tab. 4:
Settings in the "Configure Set Variable Value" dialogue
◾ Click the
OK
button to confirm the selection.
The "Task Configuration" dialogue appears.
◾ Click the
Save
button to confirm the selection.
The
Tasks
tab appears.
This completes setting up the task. The LED strip
illuminates "red" when the vandalism sensor has the
status "Alarm".
Task 2: Motion sensor
◾ Switch to the
Tasks
tab.
◾ Place the mouse cursor at the end of the first unoc-
cupied task (e.g. Task 2).
An "edit" symbol appears and the mouse cursor
changes to a "hand" symbol.
◾ Click the "edit" symbol.
The "Task Configuration" dialogue appears.
Fig. 7:
"Task Configuration" dialogue
◾ Link in the "Trigger Expression" group box the status
of the motion sensor with the value "Alarm" via the
"=" operator.
◾ Ensure that the following settings are activated for
the individual parameters in the "Details" group box.
Parameter
Setting
Enable
Active
Name
Task 2
Description
GREEN Motion
Delay
0
Delay Mode
Switch on Delay
Action
Set Variable Value
Tab. 5:
Settings in the "Task Configuration – Details" dialogue
◾ Click the
Setup
button
The "Configure Set Variable Value" dialogue appears.
Fig. 8:
"Configure Set Variable Value" dialogue
◾ Ensure that the following settings are activated for
the individual parameters.
Parameter
Setting
Device
CMCIII-IO3
Variable
Output 2.Relay
Value on True
On
Value on False
Off
Tab. 6:
Settings in the "Configure Set Variable Value" dialogue
◾ Click the
OK
button to confirm the selection.
The "Task Configuration" dialogue appears.
◾ Click the
Save
button to confirm the selection.