![FRIEDHELM LOH Rittal 1194.42 Series Assembly And Operating Instructions Manual Download Page 7](http://html1.mh-extra.com/html/friedhelm-loh/rittal-1194-42-series/rittal-1194-42-series_assembly-and-operating-instructions-manual_2332675007.webp)
8 Handling instructions
Page 7
of
28
Rittal cooling unit assembly and operating instructions
5.1.8 Compressor: On / Off
Switching the compressor ON: press UP for more
than 3 s (when pressing the button, the display
shows ON).
Switching the compressor OFF: press UP for more
than 3 s. The display shows the message “OFF”.
In OFF status, the following functions are disabled (if
featured by the model):
compressor control
duty setting
continuous cycle
5.2 Alarm parameters
A0: Alarm temperature differential
This represents the differential used to activate the
high temperature alarm (“AH”) .In the event of an
alarm, as seen in the figure, the value of “A0” deter-
mines the actual activation of the temperature alarm.
The value of “A0” (negative or positive) defines the na-
ture of alarm “AH” (absolute or relative):
A0 ≤ 0
AH expressed as absolutes
A0 > 0
AH expressed relative to the set point
Figure 4: High temperature alarm
AH: High temperature alarm
AH setting: 10 degrees is the factory setting (-50 to 99
is the lower and upper limit ). Other Factory settings:
Setpoint (ST) = 35°C; A0 = 2°C.
For example: If the internal temperature of the cabinet
is Ti = 46°C, ST (35°C)+ AH (10°C) = 45°C ,
so 46°C > 45°C the display will show AH-alarm. As
long as Ti is more than 43°C the display will show AH-
alarm, because ST (35°C)+ AH (10°C) - A0 (2°C) =
43°C. If the temperature Ti will fall to 42°C the alarm
AH will no longer be shown in the display. As long as
the temperature inside of the cabinet will not rise over
45°C again there will be no AH-alarm displayed.
Temperature alarm output
Logo and buzzer on display: The information
“AH” and logo will be shown on the display and
buzzer.
The over temperature message may also be
polled via a contact on the connection clamp of
the cooling unit (system message relay with
changeover contact, see connection diagrams).
--Terminal
“
1
”
C (connection of the supply voltage
to the fault signal relay)
--Terminal
“
2
”
NO (normally open) .
Notice!
Delay for high temperature alarm when
power ON: When alarm condition is
achieved but power is ON, the timer
start to count for a specify value (Ad1).
Alarm relay becomes active when this
time is elapsed.
Notice!
The unit of parameter “Ad” is “Sec”.
The unit of parameter “Ad1” is “Min”.
Notice!
The contacts of the relays are normally
open (NO). If the alarm occurs the con-
tacts close (NC).
HP
:
High pressure alarm output
Logo and buzzer on display: The information
“HP” and logo will be shown on the display and
buzzer.
The over temperature message may also be
polled via a contact on the connection clamp of
the cooling unit (system message relay with
changeover contact, see connection diagrams).
--Terminal
“
1
”
C (connection of the supply voltage
to the fault signal relay)
--Terminal
“
2
”
NO (normally open) .
Notice!
Delay for high temperature alarm when
power ON: When alarm condition is
achieved but power is ON, the timer
start to count for a specify value (Ad1).
Alarm relay becomes active when this
time is elapsed.
Notice!
The unit of parameter “Ad” is “Sec”.
The unit of parameter “Ad1” is “Min”.
Notice!
The contacts of the relays are normally
open (NO). If the alarm occurs the con-
tacts close (NC).
5.3 Evaluating system messages
Display
screen
Buzzer
Alarm
relay
System
message
Measures
Summary of Contents for Rittal 1194.42 Series
Page 14: ...12 Wire plan Rittal cooling unit assembly and operating instructions page 14 of 28...
Page 15: ...12 Wire plan Rittal cooling unit assembly and operating instructions page 15 of 28...
Page 17: ...1 page17 of 27 1 2 3 4 50 200mm 2 5 30 5 1 1 3 5K Ti 5 1 1 3 7 H1...
Page 24: ...9 page 24 of 27 9 2 15 16 17 18 19 20 1 21 2...
Page 25: ...9 page 25 of 27 22 23 24 10 11 1 1 1 4 25...
Page 26: ...12 page 26 of 27 12...
Page 27: ...12 page 27 of 27 X2 M3 X3 B1 X1 K1 M1 K2 M2 F2...