FRIEDHELM LOH Rittal 1194.42 Series Assembly And Operating Instructions Manual Download Page 3

1 Application 

Rittal cooling unit assembly and operating instructions  

 

page 

3

 of 27 

1  Application 

Enclosure cooling units are designed and built to dis-
sipate heat from enclosures by cooling the air inside 
the  enclosure  and  protecting  temperature  sensitive 
components. 

2  Technical data 

See nameplate  

3  Assembly 

The standard wall-mounted unit is suitable for exter-
nal mounting. Cut out the sections and drill according 
to the drawing.  
Cut the enclosed seals to the required length and at-
tach to the unit. Screw tapped pins into the blind nuts 
on the rear of the unit. The unit is then to be secured 
using washers and nuts 

4  Safety notes 

The  following  safety  notices  are  to  be  observed  in 
their entirety for the correct use of the equipment: 
 

  To prevent the enclosure with the cooling unit fit-

ted tipping over, it is essential that this be bolted 
to the floor. 

  A roller door is to be used to ensure problem free 

opening and closing of the enclosure door.  

  A  transportable  enclosure  with  built-in  cooling 

unit  may  only  be  produced  if  an  additional 
transport anchorage to support the cooling unit is 
used.  
Prior to mounting, ensure that:  

  the site for the enclosure, and hence the arrange-

ment to the cooling unit, is selected so as to en-
sure good ventilation;  

  the location is free from excessive dirt and mois-

ture,  

  the cutout for air extraction is located in the upper 

area of the enclosure; 

  the  mains  connection  ratings,  as  stated  on  the 

rating plate. are available:  

  the ambient temperature does not 50°C;  

  The  packaging  shows  no  signs  of  damage. 

Traces of oil on damaged packaging are an indi-
cation  of  refrigerant  loss  and  of  leakage  in  the 
unit system. Any damage to the packaging may 
be the cause of subsequent malfunctions:  

  the enclosure is sealed on an sides              Con-

densation will occur if the enclosure is leaky;  

  the separation of the units from one another and 

from the wall should not be less than 200mm;  

  air inlet and outlet are not obstructed on the in-

side of the enclosure;  

  units  are  only fitted  horizontally  in  the  specified 

position Max. deviation from the true horizontal: 
2°  

  condensate drainage is provided  

  electrical  connection  and  repair  are  carried  out 

only by authorized personnel  

  Use only original replacement  parts and  acces-

sories.  

  Losses from the components installed in the en-

closure must not exceed the specific refrigeration 
capacity of the cooling unit itself;  

  The customer may not modify the cooling unit in 

any way. 

Commencing operation and 
control behavior 

Following the completion of mounting and a waiting 
period of approximately 30 minutes (to allow oil to col-
lect in the compressor in order to ensure lubrication 
and cooling). 

5.1  Controller control 

 

Figure 1: Controller 

 
After  electrical  connection  the  internal  fan  turns  on 
and  circulates  the  enclosure  air.  This  helps  assure 
even  temperature  distribution  within  the  enclosure. 
The condenser fan and compressor are controlled by 
the controller. The minimum time is 3 minutes to re-
start  the  compressor  after  it  has  switched  off.  The 
switching difference is 5 K. To avoid short switching 
cycles and  hence  the  danger  of  inadequate  or only 
partial cooling in some sections of the enclosure, The 
switching difference should be set to be only as low 
as necessary. For economic reasons (energy saving), 
the nominal value of the internal enclosure tempera-
ture Ti should also be set to be only as low as neces-
sary. 

5.1.1 Operation of the controller 

The  display  terminal  H1  consists  of  a  3  position  7-
segment  display  which  indicates  the  internal  enclo-
sure  temperature  in  °C  as  well  as  any  fault  codes. 
The  actual  enclosure  internal  temperature  is  con-
stantly displayed on H1. When a system message is 
generated, this alternates in the display with the cur-
rent internal enclosure temperature. 

Summary of Contents for Rittal 1194.42 Series

Page 1: ...Assembly and operating instructions 3370 22X 3370 52X 3370 32X 3370 62X 3370 37X 3370 72X 3370 42X 1194 42X 1194 55X 1194 62X 1194 72X Compact Cooling unit Compact...

Page 2: ...eters Error Bookmark not defined 5 3 Evaluating system messages Error Bookmark not defined 5 4 Forced cooling Error Bookmark not defined 6 Filter mats Error Bookmark not defined 7 Technical informatio...

Page 3: ...l occur if the enclosure is leaky the separation of the units from one another and from the wall should not be less than 200mm air inlet and outlet are not obstructed on the in side of the enclosure u...

Page 4: ...e set point C r2 Setpoint max value r1 50 45 C cc Continuous cycle period 0 15 1 hours C A0 Alarm and fan dif ferential 20 20 2 See chapter 5 2 F AH Alarm maximum temp 50 99 10 See chapter 5 2 C Ad1 D...

Page 5: ...mperature range Press the SET button for more than 3 s if there are active alarms mute the buzzer the display shows the parameter code PS password press the SET button to access the password set ting...

Page 6: ...havior Rittal cooling unit assembly and operating instructions page 6 of 28 Reconnect power supply while holding but tons 2 and 3 Display will show the message CF After a few seconds the unit will res...

Page 7: ...no AH alarm displayed Temperature alarm output Logo and buzzer on display The information AH and logo will be shown on the display and buzzer The over temperature message may also be polled via a con...

Page 8: ...connected by suitable Pipe work This circuit is filled with a readily boiling substance the refrigerant The R134a CH2FCF3 refrigerant is free from chlo rine It has an ozone destroying potential ODP of...

Page 9: ...ooling unit Cut the supplied sealing tape to the correct length and stick it carefully along the back of the unit so that no gaps are left at the joints Figure 8 Applying the self adhesive tape Screw...

Page 10: ...sites with a continuous current carrying capacity incoming mains power supply of more than 100 A per phase and with a supply voltage of 400 230 V If necessary the electricity supply company must be co...

Page 11: ...tensity Notice Caution Risk of fire Never use flammable liquids for cleaning Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filter if necessary Cooling membranes s...

Page 12: ...19 Twist off the screw of the outside fan 1 Figure 20 Twist off the screw of the outside fan 2 Figure 21 Remove the outside fan Figure 22 Disconnect the plug of the outside fan 1 Figure 23 Disconnect...

Page 13: ...plant Please contact us for advice 11 Scope of supply and guarantee 1 cooling unit ready for connection 1 sealing tape 1 set of mounting and operating instructions Guarantee This unit is covered by a...

Page 14: ...12 Wire plan Rittal cooling unit assembly and operating instructions page 14 of 28...

Page 15: ...12 Wire plan Rittal cooling unit assembly and operating instructions page 15 of 28...

Page 16: ...17 2 17 3 17 4 17 5 17 5 1 17 5 1 1 17 5 1 2 18 5 1 3 18 5 1 4 19 5 1 5 19 5 1 6 19 5 1 7 19 5 1 8 19 5 2 20 5 3 20 5 4 20 6 21 7 21 7 1 1 21 7 1 2 21 8 21 8 1 22 8 1 1 22 8 1 2 22 8 2 1 23 8 2 2 23...

Page 17: ...1 page17 of 27 1 2 3 4 50 200mm 2 5 30 5 1 1 3 5K Ti 5 1 1 3 7 H1...

Page 18: ...SET UP DOWN SET SET 3 C SET 3 PS SET UP DOWN 22 SET UP DOWN LED LED SET UP DOWN SET SET 3 F PS 0 99 22 22 S St r1 r2 35 St r1 r2 St F rd 0 19 5 r4 rd C C r1 20 r2 30 R1 R2 C r2 r1 50 45 C cc 0 15 1 h...

Page 19: ...e 19 of 27 S SET 1 UP DOWN SET 5 1 4 35 S 5 1 5 SET 3 PS SET UP DOWN 22 SET UP DOWN r1 r2 SET UP DOWN SET SET 3 r1 r2 5 1 6 2 1 2 99 99 5 1 7 3 Start up reset 1 3 2 1 3 22 2 3 CF 5 1 8 UP 3 ON UP 3 OF...

Page 20: ...of 27 5 2 A0 AH A0 A0 AH A0 0 AH A0 0 AH 4 AH AH 10 50 99 ST 35 AO 2 AH 10 46 ST 35 AH 10 45 46 45 AH 45 AH AH 42 ST 35 AH 10 AO 2 43 42 43 43 AH 1 C 2 Ad1 Ad1 Ad Ad1 HP HP 1 C 2 HP HP 1 C 2 5 3 E0 HI...

Page 21: ...9 page 21 of 27 AH set 3 22 CC 0 1 UP DOWN 3 cc 2 6 5 7 R134a CH 2FCF3 ODP 7 1 1 6 7 1 2 7 8 30 000...

Page 22: ...9 page 22 of 27 7 1 70 Rittal 8 1 1 2 8 TS SK 3370724 TS 8800 071 8 1 1 9 10 3370220 compact 8 1 2 4 11 12 13 8 2...

Page 23: ...1 N SK 1194424 L1 L2 SK 3370520 L1 N SK 3370524 L1 L2 SK 1194550 L1 N SK 1194554 L1 L2 SK 3370620 L1 N SK 1194620 L1 N SK 3370724 L1 L2 SK 1194724 L1 L2 8 2 1 3mm K 8 2 2 10 IEC 61 000 3 11 100A 400 2...

Page 24: ...9 page 24 of 27 9 2 15 16 17 18 19 20 1 21 2...

Page 25: ...9 page 25 of 27 22 23 24 10 11 1 1 1 4 25...

Page 26: ...12 page 26 of 27 12...

Page 27: ...12 page 27 of 27 X2 M3 X3 B1 X1 K1 M1 K2 M2 F2...