Thermozone AD Corinte W
13
AD Corinte W - low temperature coil
In-/outlet water temperature 70/40˚C*
Inlet air tempe15˚C
Inlet air tempe20˚C
Typ
Airflow
[m
3
/h]
Output
[kW]
Air temp.
out
[˚C]
Water-
-
flow
[l/s]
Output
[kW]
Air temp.
out
[˚C]
Water-
flow
[l/s]
ADC17
max
3000
21.8
36
0.17
18.5
38
0.14
min
1400
13.5
43
0.10
11.5
44
0.09
ADC22
max
4000
30.7
37
0.24
26.2
39
0.20
min
1800
18.4
45
0.14
15.8
45
0.12
ADC25
max
4500
35.1
38
0.27
30.0
39
0.23
min
2050
21.2
45
0.16
18.2
46
0.14
In-/outlet water temperature 60/40˚C
Typ
[m
3
/h]
[kW]
[˚C]
[l/s]
[kW]
[˚C]
[l/s]
ADC17
max
3000
19.4
34
0.23
16.2
36
0.19
min
1400
12.0
40
0.14
10.1
41
0.12
ADC22
max
4000
27.0
35
0.32
22.8
37
0.27
min
1800
16.1
41
0.19
13.7
42
0.16
ADC25
max
4500
30.8
35
0.36
26.0
37
0.31
min
2050
18.5
42
0.22
15.7
43
0.18
Typ
[m
3
/h]
[kW]
[˚C]
[l/s]
[kW]
[˚C]
[l/s]
ADC17
max
3000
14.4
29
0.11
10.9
31
0.08
min
1400
9.2
34
0.07
7.1
35
0.05
ADC22
max
4000
20.7
30
0.16
15.9
32
0.12
min
1800
12.8
36
0.10
10.0
36
0.07
ADC25
max
4500
23.8
31
0.18
18.5
32
0.14
min
2050
14.8
36
0.11
11.6
37
0.09
Typ
[m
3
/h]
[kW]
[˚C]
[l/s]
[kW]
[˚C]
[l/s]
ADC17
max
3000
16.1
31
0.19
12.9
33
0.15
min
1400
10.0
36
0.11
8.1
37
0.09
ADC22
max
4000
22.6
32
0.27
18.2
33
0.21
min
1800
13.6
37
0.16
11.1
38
0.13
ADC25
max
4500
25.9
32
0.30
21.0
34
0.25
min
2050
15.7
38
0.18
12.8
38
0.15
Inlet air tempe15˚C
Inlet air tempe20˚C
Airflow
Output
Air temp.
out
Water-
flow
Output
Air temp.
out
Water-
flow
In-/outlet water temperature 60/30˚C
Inlet air tempe15˚C
Airflow
Output
Air temp.
out
Water-
flow
Inlet air tempe20˚C
Output
Air temp.
out
Water-
flow
In-/outlet water temperature 55/35˚C
Inlet air tempe15˚C
Inlet air tempe20˚C
Airflow
Output
Air temp.
out
Water-
flow
Output
Air temp.
out
Water-
flow