17
AC Corinte
Technical specifications |
Thermozone AC Corinte E with electrical heat
3
Type
Output
steps
[kW]
Airflow
[m
3
/h]
∆
t
*2
[°C]
Sound
level
*3
[dB(A)]
Voltage
motor
[V]
Voltage
heat
[V]
Amperage
motor
[A]
Amperage
heat
[A]
Height/
Length
[mm]
Weight
[kg]
ACC10E
*1
0/6/9
950/1900
29/14
44/61
230V~
400V3~
2,2
8,7/13,0
1000
47
ACC15E
*1
0/8/12
1350/2600
27/14
45/62
230V~
400V3~
2,9
11,5/17,3
1500
63
ACC20E
0/12/18
1980/3800
28/14
47/64
230V~
400V3~
4,3
17,3/26,0
2000
95
ACC25E
0/12/18
2340/4500
23/12
48/65
230V~
400V3~
5,1
17,3/26,0
2500
110
ACC30E
0/16/24
2660/5100
27/14
48/65
230V~
400V3~
5,8
23,1/34,6
3000
126
*
1
) ACC1000E and ACC1500E is available only for horizontal mounting.
*
2
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
3
) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m
2
.
Technical specifications |
Thermozone AC Corinte WL with water heat, coil for low tempered water <80/60 °C
2
Type
Output
*2
[kW]
Airflow
[m
3
/h]
∆
t
*2,3
[°C]
Water
volume
[l]
Sound level
*4
[dB(A)]
Voltage
motor
[V]
Amperage
[A]
Height/
Length
[mm]
Weight
[kg]
ACC10WL
*1
19
950/1900
42/35
2,0
44/61
230V~
2,1
1000
47
ACC15WL
*1
29
1350/2600
41/34
3,2
45/62
230V~
2,9
1500
63
ACC20WL
42
1980/3800
40/33
4,3
47/64
230V~
4,3
2000
95
ACC25WL
52
2340/4500
41/34
5,4
48/65
230V~
5,0
2500
110
ACC30WL
60
2660/5100
38/31
6,6
48/65
230V~
5,7
3000
126
Technical specifications |
Thermozone AC Corinte WH with water heat, coil for high tempered water >80/60 °C
2
Type
Output
*2
[kW]
Airflow
[m
3
/h]
∆
t
*2,3
[°C]
Water
volume
[l]
Sound
level
*4
[dB(A)]
Voltage
motor
[V]
Amperage
[A]
Height/
Length
[mm]
Weight
[kg]
ACC10WH
*1
11
950/1900
26/20
1,1
44/61
230V~
2,1
1000
47
ACC15WH
*1
17
1350/2600
26/20
1,9
45/62
230V~
2,9
1500
63
ACC20WH
24
1980/3800
25/19
2,5
47/64
230V~
4,3
2000
95
ACC25WH
30
2340/4500
25/23
3,3
48/65
230V~
5,0
2500
110
ACC30WH
35
2660/5100
23/17
3,9
48/65
230V~
5,7
3000
126
*
1
) ACC1000W and ACC1500W is available only for horizontal mounting.
*
2
) Applicable at water temperature 80/60 °C, air temperature in +15 °C.
*
3
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
4
) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m
2
.
Protection class AC Corinte E/W (IP20).
CE compliant.