61
SWX EX12, SWX EX22
Appendix A
Technical data
Type
SWX EX12
SWX EX22
Power supply
3~230/400V
3~230/400V
Current consumption,
A
0.43 / 0.25
0.88 / 0.51
Air volume
m³/h
2250
4150
Sound level
dB
61
67
Throw length
1)
m
8
10
Connecting pipe
mm
Ø22
Ø28
Max. working temp. water
°C
125
125
Max. working pressure (of water)
bar
16
16
Ambient temperature
°C
-20 °C - +40 °C
-20 °C - +40 °C
Weight
kg
25
42
Protection class, fan motor
IP44
IP44
1)
Measured 5 metres in front of the SWX.
Water temp.
in/out 90 °C/70 °C
in/out 80 °C/60 °C
in/out 60 °C/40 °C
Air
flow
Supply
air
Output
air
Power
Flow
water
Pressure
drop
water
Output
air
Power
Flow
water
Pressure
drop
water
Output
air
Power
Flow
water
Pressure
drop
water
m³/h
°C
°C
kW
l/s
kPa
°C
kW
l/s
kPa
°C
kW
l/s
kPa
SWX EX 12
2250
+5
43,4
30,5
0,38
12,0
37,8
26,0
0,37
9,0
26,3
16,9
0,21
4,2
SWX EX 12
2250
+15
48,6
25,6
0,37
8,6
42,8
21,2
0,20
6,2
31,1
12,3
0,15
2,3
SWX EX 22
4150
+5
42,5
54,9
0,68
18,7
37,1
47,0
0,58
14,2
26,1
30,9
0,38
6,8
SWX EX 22
4150
+15
47,8
46,2
0,57
13,6
42,3
38,5
0,47
9,8
31,0
22,6
0,27
3,8
Capacity SWX EX12-22
Dimensions
A mm
B mm
C mm
D mm
E mm
F mm
G mm
H mm
Ø I
SWX EX12
550
530
380
630
Ø22
250
330
410
10
SWX EX22
705
655
430
700
Ø28
270
420
505
10
Dimensions SWX EX