Installation and operating instructions

General Instructions 

Read these instructions carefully prior to 

installation and use. Keep this manual for 

future reference.

The product may only be used as set out in 

the assembly and operating instructions. The 

guarantee is only valid should the product be used 

in the manner intended and in accordance with 

the instructions. 

 

Application 

Pamir creates an efficient temperature dividing 

air barrier in door openings.  

Pamir 3500 has a recommended installation 

height of 3,5 m.

Pamir 4200 has a recommended installation 

height of 4,2 m.

Pamir 5000 has a recommended installation 

height  of 5,0 m. 

Pamir air curtains are available in 3 versions: 

without heat (ambient), with electrical heating, 

or with water heating. 

Protection class for units with electrical heating: 

IP20. 

Protection class for units without heating and 

units with water heating: IP24 (IP21 when 

vertically mounted to the left, seen from the 

inside.)   

Operation 

Air is drawn in at the top/rear of the unit and 

blown downwards/outwards shielding the 

door opening and minimizing heat loss. To 

achieve the optimum air curtain effect the unit 

must extend the full height/width of the door 

opening.

The grille for directing the outlet air is 

adjustable and is normally angled outwards to 

achieve the best protection against incoming 

air. 

The efficiency of the air curtain depends on 

the air temperature, the pressure differencial 

across the doorway and any wind load. 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 

curtain. The ventilation should therefore be 

balanced. 

Horizontal mounting 

The air curtain is installed horizontally with the 

outlet air grille facing downwards as close to 

the door as possible. Minimum distance from 

outlet to floor for electrically heated units is 

1800 mm. For other minimum distances, see 

fig. 3. 

For the protection of wider openings, several 

units can be mounted next to each other using 

a joining kit PA3JK/PA4JK. 

The design kit which conceals cables, pipes 

and mountings is available for both wall and 

ceiling installations. 

 

Mounting with wall brackets 

Wall brackets PA34WB and PAWBL are available 

as accessories. 

1. Remove the plastic covers on the wall 

brackets. (Fig. 6A)

2. Mount the brackets on the wall according to 

the dimensions fig. 6B.

3. Fasten the hammerhead screws on the unit 

in the holes M8. (Fig. 5 and 6C)

4. Lock the nuts so that the hammerhead 

screws are at 20 mm height. Note the 

direction of the screw heads. (Fig. 6C)

5. Slide the unit on the consoles. (Fig. 6D)

6. Lock the nuts against the bracket and return 

the plastic covers. (Fig. 6E) 

Horizontal mounting on the ceiling 

Threaded rods, wire suspension kits and ceiling 

brackets for ceiling mounting are available 

as accessories, see fig. 7 and 8 and separate 

manuals.

 

Horizontal recessed mounting in false ceilings

Outlet extension used for recessed installation 

is available as an accessory, see fig. 10 and 

separate manual.

 

Mounting 

The air curtain range can be adapted for 

vertical or horizontal installation. The units can 

also be installed by recessing into suspended 

ceilings.

The product must be mounted in such a way to 

allow future service and maintenance. Ensure 

that the front panel/service hatch is accessible 

and can be fully opened.

 

Summary of Contents for PAFEC3510A

Page 1: ...Pamir 3500 4200 5000 21 EN 26 SE Original instructions 32 NO 38 FR 44 DE 50 NL 56 ES 62 IT 68 PL 74 RU 81 FI DK 87 ...

Page 2: ...ldingen Voor een vertaling van de gebruikte Engelse teksten zie de pagina s van de resp taal NL Las páginas introductorias contienen básicamente imágenes Consulte la traducción de los textos en inglés que las acompañan en las páginas del idioma correspondiente ES Le pagine introduttive contengono prevalentemente immagini Per le traduzioni dei testi scritti in inglese vedere le pagine nelle diverse...

Page 3: ... x M8 205 92 364 A Pamir 3500 L mm A mm PAFEC3510 1039 40 PAFEC3515 1549 40 PAFEC3520 2039 40 PAFEC3525 2549 39 DN20 3 4 outside thread FC 2 m 2 5 m L1 mm L2 mm PAFEC3515 1572 1515 PAFEC3520 2062 2004 PAFEC3525 2572 2515 270 36 525 L1 L2 23 40 Vertical mounting Horizontal mounting ...

Page 4: ...r 4200 5000 DN20 3 4 outside thread FC 2 m 2 5 m L mm A mm PAFEC4210 5010 1039 40 PAFEC4215 5015 1549 40 PAFEC4220 5020 2039 40 PAFEC4225 5025 2549 39 295 36 611 40 23 L2 L1 L1 mm L2 mm PAFEC4215 5015 1572 1515 PAFEC4220 5020 2062 2004 PAFEC4225 5025 2572 2515 Vertical mounting Horizontal mounting ...

Page 5: ...ces on both sides must be loosened When the front is reinstalled it is important to ensure that it is firmly seated in the front locks min 100 Fig 3 Minimum distance Fig 2 PC board FC is integrated within the air curtain at delivery PC board FC Gland Terminal block Gland Service hatch Loosen Remove ...

Page 6: ...0 4200 5000 6 B A Fig 4b Filling the water coil vertical mounting A B C D Water connection 2 Fig 4a NOTE Use a pipe wrench or a similar tool to grip the air curtain connections to prevent straining of the pipes ...

Page 7: ...C4210 750 PAFEC5010 750 PAFEC3515 1260 PAFEC4215 1260 PAFEC5015 1260 A mm B mm PAFEC3500 205 92 PAFEC4200 235 102 PAFEC5000 235 102 PAFEC 3510 3515 4210 4215 5010 5015 PAFEC3520 4220 5020 PAFEC3525 4225 5025 A B A 127 L B 127 875 875 A B 127 770 745 745 A B A 127 L B 127 875 875 A B 127 770 745 745 M8 holes for mountings ...

Page 8: ...0 mm 18045 PA34WB20 PAFEC 3520 4220 5020 3 pcs 400 mm 18046 PA34WB30 PAFEC 3525 4225 5025 4 pcs 400 mm 214951 PAWBL15 PAFEC 3510 3515 4210 4215 5010 5015 2 pcs 560 mm 214952 PAWBL20 PAFEC 3520 4220 5020 3 pcs 560 mm 214953 PAWBL30 PAFEC 3525 4225 5025 4 pcs 560 mm A 19 D 11 E C B mm PA34WB PAWBL A 80 120 B 40 60 C 40 52 5 D 120 165 E 40 60 F 400 560 G 408 568 Accessories horizontal mounting ...

Page 9: ...5 PAFEC 3510 3515 4210 4215 5010 5015 4 pcs 18060 PA34CB20 PAFEC 3520 4220 5020 6 pcs 18061 PA34CB30 PAFEC 3525 4225 5025 8 pcs 18062 PA34WS15 PAFEC 3510 3515 4210 4215 5010 5015 4 pcs 3 m 18063 PA34WS20 PAFEC 3520 4220 5020 6 pcs 3 m 18064 PA34WS30 PAFEC 3525 4225 5025 8 pcs 3 m 18056 PA34TR15 PAFEC 3510 3515 4210 4215 5010 5015 4 pcs 1 m 18057 PA34TR20 PAFEC 3520 4220 5020 6 pcs 1 m 18058 PA34TR...

Page 10: ...130 200 mm 19086 PA3XT15 PAFEC 3515 130 200 mm 19087 PA3XT20 PAFEC 3520 130 200 mm 19088 PA3XT25 PAFEC 3525 130 200 mm 19090 PA4XT10 PAFEC 4210 5010 130 200 mm 19091 PA4XT15 PAFEC 4215 5015 130 200 mm 19092 PA4XT20 PAFEC 4220 5020 130 200 mm 19093 PA4XT25 PAFEC 4225 5025 130 200 mm See separate manual for PA3DC PA4DC Item number Type Length 13552 PA3DCS PAFEC 3500 200 300 mm 13553 PA3DCM PAFEC 350...

Page 11: ...Type 110759 PA3JK PAFEC 3500 110760 PA4JK PAFEC 4200 5000 110751 PA3VDW15 PAFEC 3515 110752 PA3VDW20 PAFEC 3520 110753 PA3VDW25 PAFEC 3525 110754 PA4VDW15 PAFEC 4215 5015 110755 PA4VDW20 PAFEC 4220 5020 110756 PA4VDW25 PAFEC 4225 5025 PA3HE PAFEC 3500 PA4HE PAFEC 4200 5000 PA3HEVDW PAFEC 3500 PA4HEVDW PAFEC 4200 5000 10028 AXP300 PAFEC 3500 4200 5000 See separate manual for PA3VDW PA4VDW 3 2 PA3VD...

Page 12: ...00S PAFEC 3500W 4200W 5000W 18055 FHDN20 PAFEC 3500W 4200W 5000W 350 mm 88906 FHDN2010 PAFEC 3500W 4200W 5000W 1000 mm PA34EF DTV200S Accessories 2 See separate manual FHDN SDM VKF VPFC Valve systems Item number Type Connection Flow range l s 238293 VPFC15LF DN15 0 012 0 068 238294 VPFC15NF DN15 0 024 0 13 238295 VPFC20 DN20 0 058 0 32 238296 VPFC25 DN25 0 10 0 60 238297 VPFC32 DN32 0 22 1 03 See ...

Page 13: ...FCRTX 39x39x23 mm 74695 FCOTX 39x39x23 mm 74699 FCLAP 89x89x26 mm 74702 FCWTA for water heated units 17495 FCDC 74718 FCBC05 5 m 74719 FCBC10 10 m 74720 FCBC25 25 m 74721 FCSC10 10 m 74722 FCSC25 25 m 74703 FCTXRF for FC Smart FC Pro 89x89x26 mm Accessories FCDA FC Direct FCSA FC Smart FCPA FC Pro FCBA FC Building FCLAP See separate manual for FC FCBC10 FCDC FCCF FCLAP FCBC10 FCDC FCCF FCLAP FCTXR...

Page 14: ...ing Trafo N Motor 230V L Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND 3510 2 Motors 3515 3 Motors 3520 4 Motors 3525 5 Motors 4210 5010 3 Motors 4215 5015 4 Motors 4220 5020 6 Motors 4225 5025 7 Motors PAFEC ARFEC 5000 A PAFEC ARFEC 4200 A PAFEC ARFEC 3500 A ...

Page 15: ...C ARF FCBASEPCB REA Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination PAFEC ARF N L3 L2 L1 M M M Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo N Motor 230V L PE 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND 400V 3 Outlet sensor 3510 2 Motors 3515 3 Motors 4210 5010 3 Motors 4215 5015 4 Motors PAFEC ARF ...

Page 16: ... M K2 K1 TS3 TS4 400V 3 2 X 400V 3 PAFEC4220E 4225E L3 L2 L1 N L3 L2 L1 M Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo N Motor 230V L PE 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND Outlet sensor 3520 4 Motors 3525 5 Motors 4220 5020 6 Motors 4225 5025 7 Motors PAFEC3520E 3525E Wiring diagrams for control system in the FC manual PAFEC3520 25 E PAFEC4220 25 E PAFEC5020 25 E ...

Page 17: ...ensor A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE Actuator 24V WTA 12V HI LO GND 12V HI LO BUS 1 BUS 2 E1 E2 GND Outlet sensor 3510 2 Motors 3515 3 Motors 3520 4 Motors 3525 5 Motors 4210 5010 3 Motors 4215 5015 4 Motors 4220 5020 6 Motors 4225 5025 7 Motors PAFEC ARFEC 5000 W PAFEC ARFEC 4200 W PAFEC ARFEC 3500 W Wiring diagrams for control system in the FC manual ...

Page 18: ...1800 27 13 76 44 60 340 2 3 400V3 11 7 37 189580 PAFEC3515E12 3 9 7 8 12 1400 2700 26 13 79 46 63 510 3 2 400V3 16 9 50 189584 PAFEC3520E16 5 4 11 16 1900 3500 25 14 80 47 64 670 4 1 400V3 23 4 70 189588 PAFEC3525E20 6 6 13 20 2350 4400 25 14 81 47 65 860 5 1 400V3 28 6 89 2 Water heat PAFEC3500 WL IP24 Item number Type Output 5 kW Airflow 1 m3 h t 4 5 C Water volume l Sound power 2 dB A Sound pre...

Page 19: ...0 30 15 78 46 62 505 3 2 400V3 16 9 44 230361 PAFEC4215E18 6 0 12 18 1800 3500 30 15 80 47 64 675 4 1 400V3 26 64 230366 PAFEC4220E24 7 8 16 24 2300 4700 30 15 81 48 65 1015 6 0 400V3 33 8 85 230371 PAFEC4225E30 9 9 20 30 3100 6150 29 15 83 50 67 1200 6 9 400V3 42 9 100 2 Water heat PAFEC4200 WL IP24 Item number Type Output 5 kW Airflow 1 m3 h t 4 5 C Water volume l Sound power 2 dB A Sound pressu...

Page 20: ...ype Output steps kW Airflow 1 m3 h t 4 C Sound power 2 dB A Sound pressure 3 dB A Motor W Amperage motor A Voltage V Amperage A heat Weight kg 230376 PAFEC5010E12 3 9 7 8 12 900 2950 40 12 80 34 66 710 4 4 400V3 16 9 46 230380 PAFEC5015E18 6 0 12 18 1350 4200 40 13 84 35 68 935 5 6 400V3 26 66 230384 PAFEC5020E24 7 8 16 24 1700 5900 40 12 86 39 70 1420 8 1 400V3 33 8 86 230388 PAFEC5025E30 9 9 20 ...

Page 21: ...duces the efficiency of the air curtain The ventilation should therefore be balanced Horizontal mounting The air curtain is installed horizontally with the outlet air grille facing downwards as close to the door as possible Minimum distance from outlet to floor for electrically heated units is 1800 mm For other minimum distances see fig 3 For the protection of wider openings several units can be m...

Page 22: ...e top of the unit horizontal or on the back vertical Pierce the gland with a screwdriver before entering the cable See Fig 2 Control is supplied by 230V to the PC board Unit with electrical heating The electrical connection is made on the top of the unit horizontal or on the back vertical Pierce the gland with a screwdriver before entering the cable See Fig 2 Control is supplied by 230V to the PC ...

Page 23: ...raise the front panel The front is locked in the open position with the front hatch hook see fig 1A or removed completely see fig 1B The service hatch is removed by loosening the screws 3 After service repairs and maintenance fasten the service hatch and the front When the front is reinstalled it is important to ensure that it is firmly seated in the front locks See Fig 1B Place the front on the e...

Page 24: ...ust temperature Should the temperature exceed the preset value the overheating alarm will activate For more information see the FC manual All units Since fan motors and other components are maintenance free no maintenance other than cleaning is necessary The level of cleaning can vary depending on local conditions Undertake cleaning at least twice a year Inlet and exhaust grilles impeller and elem...

Page 25: ...d collection point Safety For all installations of electrically heated products a residual current circuit breaker 300 mA for fire protection should be used Keep the areas around the air intake and exhaust grilles free from possible obstructions The unit must not be fully or partially covered as overheating can result in a fire risk Lifting equipment must be used to lift the unit This appliance ca...

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ...o AB Tel 46 31 336 86 00 Industrivägen 41 SE 433 61 Sävedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net Art no 189630 2020 10 26 HH CH ...

Reviews: