PA2500C

GB  

15

Assembly and operating instructions

General Instructions 

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

The product may only be used as set out in 
the assembly and operating instructions. The 
guarantee is only valid if the product is used 
in the manner intended and in accordance 
with the instructions. 

Application area 

The PA2500C air curtain unit is supplied 
without heating, with electrical heating or 
hot water heating. PA2500C is intended for 
installation heights up to 2.5 metres. The air 
curtain has an integrated control system and 
can be remotely controlled. Protection class 
for units with electrical heating: IP20.  
Protection class for units without heating and 
units with water heating: IP21.  

Operation 

Air is drawn in at the top of the unit and 
blown out downwards so that it shields the 
door opening and minimizes heat loss. To 
achieve the optimum curtain effect the 
unit must extend the full width of the door 
opening. 

The grille for directing exhaust air is 

adjustable and is normally angled outwards to 
achieve the best protection against incoming 
cold air. 

The efficiency of the air curtain depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure. 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced. 

 

Mounting 

The air curtain unit is installed horizontally 
with the supply air grille facing downwards 
as close to the door as possible. Minimum 
distance from outlet to floor for electrically 
heated units is 1800 mm. For other minimum 
distances, see fig. 4.

Mounting with wall brackets (fig. 6) 

1. Mount the brackets on the wall, see fig.6A

and dimension drawing fig.1. If the wall is 
uneven the brackets must be compensated 
for this. 

2. Hook on the unit at the lower edge of the

brackets. (Fig.6B-C)

3. Bend the top of the console over the the

unit and slide the units screws along the 
rail into the slots on the consoles. (Fig.6D) 
When the bracket is bent once, it must be 
replaced if bent back more than 45 °. 

4. Lock the nuts against the brackets. (Fig.6E)

Horizontal mounting on the ceiling  

Threaded rods, hanging brackets and ceiling 
mounting brackets for ceiling mounting are 
available as accessories, see accessories pages 
and separate manuals.

Electrical installation 

The installation, which should be preceded by 
an omnipolar switch with a contact separation 
of at least 3 mm, should only be wired by a 
competent electrician and in accordance with 
the latest edition of IEE wiring regulations. 
The control system is pre-installed in the air 
curtain. 

Unit without heating 

Connected via the built-in control board with 
1,5 m cord and plug.

Unit with water heating 

Connected via the built-in control board with 
1,5 m cord and plug.

Unit with electrical heating 

The electrical connection is made on the 
top of the unit. See Fig.2. The 3 kW unit is 
connected via the integrated control card 
using a 1,5 m cable and plug. Other units are 
intended for permanent installation. Control 
(230V~) and power supply for heat (400V3~) 
should be connected to a terminal block in 
the terminal box. 2-metre and longer units 
require dual power supplies. 

The largest cable diameter for the terminal 

block is 16 mm². The cable glands used must 
meet the protection class requirements. In 

Summary of Contents for PA2500C Series

Page 1: ...Instrukcja obs ugi PA2500C 15 GB 21 PL...

Page 2: ...t mainly of pictures For translation of the English texts used see the respective language pages GB Pocz tkowe strony zawieraj g wnie rysunki T umaczenie wykorzystanych tekst w angielskich znajduje si...

Page 3: ...5 345 min 500 min 500 min 500 157 157 157 90 5 10 20 40 22 210 165 184 1026 1536 2026 1050 1560 2050 Cu 15 53 71 40 min 500 min 500 157 157 PA2500C 3 PA2500C Gland Knock out Knock out Knock out Gland...

Page 4: ...PA2500C 4 Fig 3 Open the unit A B C TX20...

Page 5: ...30 mm 60 mm min 60 PA2500C 5 Fig 4 Fig 5 Minimum distance...

Page 6: ...min 500 mm 20 35 75 210 33 8 3x 5 10 162 PA2500C 6 Fig 6 Mounting with wall brackets Mounting with wall brackets A B C PA2510C 2 pcs PA2515C 2 pcs PA2520C 3 pcs D...

Page 7: ...DN25 VOS15LF DN15 VOS15NF DN15 VOS20 DN20 VOS25 DN25 PA34TR15 PA2510C PA2515C 1 m PA34TR20 PA2520C 1 m PA2P15 PA2510C PA2515C 1 m PA2P20 PA2520C 1 m PA2PF15 PA2510C PA2515C PA2PF20 PA2520C PAMLK PA250...

Page 8: ...V3 14 4 2050 36 1 Ambient no heat PA2500C A Type Output kW Airflow m3 h Sound level 1 dB A Voltage motor V Amperage motor A Length mm Weight kg PA2510CA 0 900 1300 43 53 230V 0 5 1050 16 PA2515CA 0 12...

Page 9: ...PA2210CA PA2215CA PA2220CA Right motor Left motor Only 2 m version PA2500C 9 PA2510CA PA2515CA PA2520CA PA2510CA PA2515CA PA2520CA...

Page 10: ...2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR M Blue Black Brown C Over heat cut out C C1 L2 PE L1 L N L3 400V 3N L2 PE L1 L N L3 230V 2210CE03 2210CE05 PA2210CE03 PA2210CE05 C3 Run...

Page 11: ...SENSOR IR C2 Over heat cut out C C1 L2 PE L1 L N L3 400V 3N Over heat C cut out PA2215CE08 PA2220CE10 M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m vers...

Page 12: ...10V HEAT ALARM WATER INTERNAL SENSOR IR PA2210CW PA2215CW PA2220CW M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid Black Brow...

Page 13: ...PAMLK C NC NO Motor alarm pot free contact M Blue Black Brown C Lo Mid Run Left motor Only 2 m version 5A x 3 5A 16A N H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTE...

Page 14: ...temp C Water flow l s Pressure drop kPa PA2510CW max 1300 5 6 30 6 0 07 5 3 min 900 4 4 32 9 0 05 3 6 PA2515CW max 2100 9 4 31 4 0 11 7 3 min 1250 6 7 34 7 0 08 4 0 PA2520CW max 2600 11 6 31 2 0 14 6...

Page 15: ...o floor for electrically heated units is 1800 mm For other minimum distances see fig 4 Mounting with wall brackets fig 6 1 Mount the brackets on the wall see fig 6A and dimension drawing fig 1 If the...

Page 16: ...able regulations and local deviations may occur the distribution board it is to be indicated that the air curtains can be supplied from more than one connection See wiring diagrams Adjustment of the a...

Page 17: ...reverse order Replacing the water coil W 1 Shut off the water supply to the unit 2 Disconnect the connections to the water coil 3 Remove the mounting screws securing the coil in the unit and lift the...

Page 18: ...nment moisture can enter the element This should not be seen as a fault but is simply rectified by connecting the appliance to the main supply via a socket without a safety cut out so that the moistur...

Page 19: ...g dip switches Unit with water heating Dip switch 3 is used for PA2DR optional OFF Actuator SD230 remove the quick connector Black Brown Blue External on off Eg time switch External potential free clo...

Page 20: ...minutes to vent out the heat if the temperature rises above 50 C again during the following 5 minutes overheating alarm is deployed The red LEDs flash and all the buttons are locked 1 Disconnect the e...

Page 21: ...s 6 1 Przymocuj wsporniki do ciany patrz rys 6A oraz rysunek wymiarowy rys 1 Je li ciana jest nier wna wsporniki nale y odpowiednio dopasowa 2 Zawie urz dzenie na dolnej kraw dzi wspornik w rys 6B C 3...

Page 22: ...pod czenia Regulacja kurtyny powietrznej i strumienia powietrza Kierunek i pr dko przep ywu powietrza nale y wyregulowa odpowiednio do r nicy temperatur r nicy ci nie i naporu wiatru zabezpieczanego...

Page 23: ...ennika wodnego W 1 Odetnij dop yw wody do urz dzenia 2 Od cz przy cza wymiennika wodnego 3 Wykr ruby mocuj ce wymiennik w urz dzeniu po czym wyjmij go z obudowy 4 Zamontuj nowy wymiennik powtarzaj c p...

Page 24: ...w miejscu o wysokiej wilgotno ci powietrza mo e doj do zawilgocenia elementu grzejnego Nie nale y tego traktowa jako usterki poniewa wystarczy pod czy urz dzenie do zasilania przez gniazdko bez wy cz...

Page 25: ...nym Prze cznik 3 przeznaczony do obs ugi czujnika drzwiowego PA2DR opcjonalny WY Si ownik SD230 usun szybkoz cze Czarny Br zowy Niebieski Zewn w wy np wy czasowy Zewn trzny styk bezpotencja owy wy PA2...

Page 26: ...ciep o Je li w ci gu kolejnych 5 minut temperatura ponownie przekroczy 50 C uruchomi si alarm przegrzania Czerwone diody LED b d pulsowa i wszystkie przyciski zostan zablokowane 1 Od cz zasilanie za p...

Page 27: ...urz dzenia Minimalne odleg o ci Monta przy u yciu uchwyt w ciennych Szt Wyposa enie dodatkowe Gland Open the unit Minimum distance Mounting with wall brackets Pcs Accessories T umaczenie pocz tkowych...

Page 28: ...e Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no 208852 201608...

Reviews: