Assembly and operating instructions

General Instructions 

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

The product may only be used as set out in 
the assembly and operating instructions. The 
guarantee is only valid if the product is used 
in the manner intended and in accordance 
with the instructions. 

 

Application area 

AR3200C is a compact air curtain for recessed 
mounting. The air curtain is available without 
heat, with electrical heating and with water 
heating. Recommended installation height for 
ambient and electrically heated units is 3,2 
metres and recommended installation height 
for water heated unit is 2,8 metres. The air 
curtain has an integrated control system and 
can also be remote controlled.  
Protection class for units with electrical 
heating: IP20.  
Protection class for units without heating and 
units with water heating: IP21. 

Operation 

Air is drawn in from underneath and blown 
out downwards so that it protects the door 
opening and minimizes heat loss. To achieve 
the optimum curtain effect the unit must 
extend the full width of the opening.  

The grille for directing exhaust air is 

adjustable and is normally angled outwards to 
achieve the best protection against incoming 
air. 

The efficiency of the air curtain depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure. 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced. 

Mounting 

The air curtain is installed horizontally with 
the supply air grille facing downwards as close 
to the door as possible, concealed in the false 
ceiling. The only visible part of the unit is 

Mounting on threaded bars inside the unit 

1. The mounting brackets (4 or 6 pcs) are fixed 

to the unit during transport. Loosen them 
and screw them into place inside the unit 
in the intended holes. In order to mount the 
brackets, remove the service hatch, outlet 
grille and covering plates. See pages 6-7.  

2. Hang on threaded bars (M8) according to fig. 

2b (accessory). 

3. Adjust the height using the lower nut so that 

the frame is in level wth the ceiling. Lock 
using the upper nut. 

Electrical installation  

The installation, which should be preceded by 
an omnipolar switch with a contact separation 
of at least 3 mm, should only be wired by a 
competent electrician and in accordance with 
the latest edition of IEE wiring regulations. 
The control system is pre-installed in the air 
curtain. 
 

the underside which is level with the ceiling. 
The service hatch must be accessible, nothing 
should prevent it being fully opened.  

The unit is ready for suspension with 

threaded bars on its outside. The threaded 
bars can also be fixed on the inside of the 
unit e.g. when mounted on a solid suspended 
ceiling.  
For the protection of wider doorways, several 
units can be mounted next to each other. 
Minimum distance from outlet to floor for 
electrically heated units is 1800 mm. 

Mounting on threaded bars outside the unit  

1. The mounting brackets (4 or 6 pcs) are fixed 

to the unit during transport. Slacken these, 
turn them around and screw into place on the 
unit according to fig. 1a.  

2. Hang on threaded bars (M8) according to fig. 

1b (accessory).  

3. Adjust the height using the lower nut so that 

the frame is in level wth the ceiling. Lock 
using the upper nut. 

Summary of Contents for AR3210C

Page 1: ...AR3200C 19 SE 26 GB Original instructions 32 FR 46 DE 54 ES 39 NO 62 IT 70 NL 78 PL 85 RU...

Page 2: ...leitungsseiten bestehen haupts chlich aus Bildern F r die bersetzung der verwendetenTexte in englischer Sprache siehe die entsprechenden Sprachseiten DE Las p ginas introductorias contienen b sicament...

Page 3: ...AR3200C 3 1028 1538 2028 1078 1588 2078 475 525 90 70 256 90 135 51 29 20 29...

Page 4: ...AR3200C 4 244 134 933 805 156 525 66 805 1315 157 Mounting on threaded bars outside the unit AR3220C AR3210C AR3215C Front view Side view...

Page 5: ...AR3200C 5 Fig 1b Mounting on threaded bars outside the unit Mounting on threaded bars outside the unit Fig 1a Mounting brackets on delivery AR3220C...

Page 6: ...R3200C 6 Mounting on threaded bars inside the unit Fig 2a Mounting brackets on delivery 124 392 E A 932 W 848 E A 851 W 935 121 124 850 1360 54 88 Top view Side view AR3220C AR3210C AR3215C W 84 121 8...

Page 7: ...Fig 2c Location of the mounting brackets on the inside of the unit AR3220C 6x AR3210C AR3215C 4x Fig 2d In order to mount the brackets remove the service hatch outlet grille and covering plates AR322...

Page 8: ...AR3200C 8 Fig 3a Snap fixings 2 1 1 2 90 AR Service hatch Fig 3b Open the unit Fig 4 Terminal box and control panel inside unit...

Page 9: ...C PA34CB20 AR3220C PA34VD15 AR3210C AR3215C PA34VD20 AR3220C PAMLK AR3200C FHDN15 AR3200C W PA2DR AR3200C PAMLK AR3200C 9 PA34TR PA2DR PA34CB PA34VD FHDN15 VOT15 DN15 VOT20 DN20 VOT25 DN25 VKF15LF DN1...

Page 10: ...tallation type E 3 Sound pressure LpA Conditions Distance to the unit 5 metres Directional factor 2 Equivalent absorption area 200 m At lowest highest airflow 4 t temperature rise of passing air at ma...

Page 11: ...flow l s Pressure drop kPa AR3210CW max 1500 8 8 35 0 05 2 4 14 1 46 0 17 23 7 min 1000 5 9 30 0 03 1 0 10 9 50 0 13 14 8 AR3215CW max 2600 15 2 33 0 08 8 5 24 5 46 0 30 92 3 min 1700 10 0 28 0 05 3 4...

Page 12: ...in 2500 14 3 36 0 14 11 2 15 6 36 0 19 18 6 Supply water temperature 55 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 55 35 C Room temperature 18 C Type Fan position Airflow...

Page 13: ...Red IR WATER ALARM HEAT 0 10V 4 3 2 1 AR3210CW AR3215CW AR3220CW Black Brown Blue Run M C Black Blue Brown AR3200CA AR3200CW F1 0 10V F2 F3 N H1H2 N on off 2 1 PE N L PE N L On Only 2 m version Right...

Page 14: ...ue N L Mid Low c1 b1 Yellow Red White Orange 230V IR WATER ALARM HEAT 0 10V 4 3 2 1 AR3210CE03 AR3210CE05 C INTERNAL SENSOR 0 10V F2 F3 N F1 H1H2 N on off 1 2 N PE L PE N L Over heat cut out C1 On L3...

Page 15: ...F2 F3 N F1 H1H2 N on off 1 2 N PE L PE N L On K1 high power K2 low power Over heat cut out C K1 K2 L3 L2 N PE L L1 400V3N M Run C Black Brown Blue MidLow N L c1 b1 White Orange Red Yellow Blue Black I...

Page 16: ...EAT 0 10V WATER ALARM 3 1 2 4 AR3215CE08 Black Right motor Run M Left motor Blue Brown Black M C Yellow Blue Red Black Blue Brown White Orange Run Black Blue Yellow Red White Orange Low L N Mid b1 c1...

Page 17: ...eat cut out Over heat cut out C K3 K4 C K2 low power K1 high power K1 K2 Low M Run Left motor C Blue Brown Black N Mid L M Right motor Run Black C Blue Brown b1 c1 Blue N Black Low Mid L b1 c1 L1 L3 L...

Page 18: ...free contact 5A x 3 5A 16A N H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR C Black Brown Blue Mid Low N L c1 b1 M Left motor Run M Right motor Run Bl...

Page 19: ...horizontally with the supply air grille facing downwards as close to the door as possible concealed in the false ceiling The only visible part of the unit is Mounting on threaded bars inside the unit...

Page 20: ...ment of the air curtain and air flow The direction and speed of the air flow should be adjusted considering the load on the opening Pressure forces affect the air stream and make it bend inwards into...

Page 21: ...returned to within the motor s operating limits Replacing the water coil W 1 Shut off the water supply to the unit 2 Open the vent valve 3 Open the drain valve 4 When the water coil is empty disconne...

Page 22: ...rty If there is no heat check the following The functions internal sensor and settings of the built in control system For units with electrical heating also check the fol lowing Power supply to electr...

Page 23: ...Factory setting dip switches Unit with water heating Dip switch 3 is used for PA2DR optional 2 1 3 Factory setting dip switches Unit without heating or with electrical heating Dip switch 3 is used for...

Page 24: ...The red LEDs flash and all the buttons are locked 1 Disconnect the electricity with the fully isolated switch 2 Determine the cause of overheating and rectify the fault 3 Connect the unit again Funct...

Page 25: ...0780 20160212 HH CH Main office Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www...