![Frico 74684 Quick Manual Download Page 16](http://html1.mh-extra.com/html/frico/74684/74684_quick-manual_2332251016.webp)
#
374
376
150 (15.0 °C)
663
664
20 (2.0 °C)
578*
0 (%)
0-100 %
579*
75 (%)
0-100 %
580*
-50 (-5.0 °C)
581*
320 (32.0 °C)
582*
180 (18.0 °C)
583*
230 (23.0 °C)
Fan speed
(%)
Outdoor
temperature
(°C)
a - #580
b - #581
c - #582
d - #583
High - #579
Low - #578
EC fans admits stepless speed control.
AC fans will automatically re-calculate to steps.
a
b
c
d
FC Frico Control - Quick guide
16
EN
Settings - Outdoor temperature sensor, requires FCOTX / FCTXRF / outdoor signal from FCBAP
Functions
Default settings
Description
*See figure below.
AC fan speed will automatically be converted to steps.
Outdoor temperature
heat blocking
0 (disabled) / 1 (enabled)
If enabled, the heat is blocked when
temperature exceeds the set point #376.
1 (enabled)
Outdoor temperature
heat blocking - set
point
Set point for Outdoor temperature heat
blocking in 0.1 °C.
Block water bypass
due to outdoor
temperature.
0 (disabled) / 1 (enabled)
If enabled, the water bypass is blocked when
temperature is above the set point #664.
1 (enabled)
Block water bypass
due to outdoor
temperature - set
point.
Set point for Block water bypass due to
outdoor temperature.
Auto fan low
Low fan speed in auto fan mode.
Auto fan high
High fan speed in auto fan mode.
Auto fan set point -
Cold high
Set point for high fan speed in cold conditions.
Auto fan set point -
Warm high
Set point for high fan speed in warm
conditions.
Auto fan set point -
Cold low
Set point for low fan speed in cold conditions.
Auto fan set point -
Warm low
Set point for low fan speed in warm conditions.
EC fans admit stepless control.
Outdoor temperature [°C]
Fan speed [%]