Output charts water AREC4000W
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
Supply water temperature:80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output*
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AREC4010W-NA
max
2550
14.7
31
0.07
2.6
28.1
50
0.34
39.6
AREC4015W-NA
max
3300
18.9
35
0.09
1.6
39.4
53
0.48
29.5
AREC4020W-NA
max
4700
27.8
30
0.13
1.5
55.4
53
0.68
25.9
AREC4025W-NA
max
5700
32.3
27
0.15
2.2
69.3
54
0.85
46.5
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output*
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AREC4010W-NA
max
2550
15.2
37
0.16
11.2
16.3
37
0.20
15.8
AREC4015W-NA
max
3300
18.8
33
0.17
5.1
22.9
38
0.28
11.8
AREC4020W-NA
max
4700
27.7
35
0.27
5.3
32.3
38
0.39
10.3
AREC4025W-NA
max
5700
32.6
35
0.28
7.2
40.1
39
0.49
19.0
Metric chart
Imperial chart
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
Supply water temperature:176 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F*
1
Water temperature: 176/140 °F
Room temperature: +64 °F
Type
Fan
position
Airflow
[cfm]
Output
[MBH]
Return
water
temp.
[°F]
Water
flow
[US gal/h]
Pressure
drop
[kPa]
Output *
2
[MBH]
Outlet
air temp.
[°F]
Water
flow
[US gal/h]
Pressure
drop
[kPa]
AREC4010W-NA
max
1501
50.2
88
68.5
2.6
95.9
122
326.2
39.6
AREC4015W-NA
max
1942
64.5
95
84.6
1.6
134.5
127
456.5
29.5
AREC4020W-NA
max
2766
94.9
86
127.5
1.5
189.1
127
643.0
25.9
AREC4025W-NA
max
3355
110.2
81
142.7
2.2
236.5
129
808.5
46.5
Supply water temperature: 140 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F*
1
Water temperature: 140/104 °F
Room temperature: +64 °F
Type
Fan
position
Airflow
[cfm]
Output
[MBH]
Return
water
temp.
[°F]
Water
flow
[US gal/h]
Pressure
drop
[kPa]
Output *
2
[MBH]
Outlet
air temp.
[°F]
Water
flow
[US gal/h]
Pressure
drop
[kPa]
AREC4010W-NA
max
1501
51.9
99
155.0
11.2
55.6
99
187.4
15.8
AREC4015W-NA
max
1942
64.2
91
163.6
5.1
78.2
100
264.4
11.8
AREC4020W-NA
max
2766
94.5
95
252.0
5.3
110.2
100
370.9
10.3
AREC4025W-NA
max
3355
111.3
95
266.3
7.2
136.9
102
466.1
19.0
AREC4000
6