background image

Connessioni / Connections 

                         X48: faston 6.35 x 0.8 mm; X52: a vite / screw, max 2.5 mmq / sqmm 

Contenitore / Case 

                         Autoesting. / Selfestinguish UL94 V0 

Gradi di protezione / Protection degrees 

                         Custodia / case X48: IP30, conn. / connect. IP20; X52: IP40, conn. / connect. IP20 

Conforme a / According to 

                         IEC 60947-2 Allegato / Annex M ed. 8 

 

3. DESCRIZIONE 

Il relè differenziale di terra è un apparecchio elettronico di protezione, a microprocessore, progettato per rilevare la corrente di fuga a basso livello o lo 

squilibrio di corrente dovuto alla perdita d'isolamento dei conduttori o dell'apparecchiatura che si desidera proteggere. 

La corrente viene rilevata attraverso il trasformatore di corrente di tipo toroidale FRER cod. TDC... o TDA..., all'interno del quale devono passare tutti i 

conduttori del circuito che si desidera proteggere. 

Il microprocessore realizza le seguenti funzioni: 

 

Taratura della corrente di intervento (TRIP) da 25 mA a 25 A suddivisa in 3 campi: 25 mA

250 mA, 250 mA

2.5 A, 2.5 A

25 A. 

 

Taratura del tempo di intervento (TRIP) da istantaneo a 5 sec suddivisa in 2 campi: ist.

0.5 sec, 0.2

5 sec. 

 

X48: comandi verso un (1) relè operativo di intervento (TRIP); X52: comandi verso due (2) relè operativi di intervento (TRIP). 

 

Test dei relè di uscita. 

 

Ripristino manuale (locale o remoto) o automatico programmabile. 

 

Controllo continuo della connessione tra il relè  e il toroide con intervento del contatto di uscita in caso di esito negativo. 

L’ ampia scala di corrente permette una facile scelta del valore della corrente d'intervento in modo tale da mantenere i valori delle tensioni di contatto al 

di sotto di 50V come richiesto dalle norme CEI 64-8. 

Lo strumento, grazie ai filtri utilizzati sui circuiti d'ingresso è immune ai disturbi esterni. Il funzionamento è assicurato anche con correnti differenziali 

alternate sinusoidali e continue pulsanti, che siano applicate bruscamente o che aumentino lentamente (tipo A secondo IEC 755). 

3. DESCRIPTION 

The Earth Leakage Relay is a microprocessor based electronic protection device designed to recognize low level leakage or unbalanced currents due to 

insulation loss on conductors or equipment that must be protected. 

The measure of the leakage currents is obtained by the use of the ring-type current transformer FRER code TDC... or TDA... . All circuit conductors to 

be protected shall go through the CT. 

The microprocessor carries up several functions, such as: 

 

Trip current adjustment 25 mA to 25 A divided in 3 ranges: 25 mA

250 mA, 250 mA

2.5 A, 2.5 A

25 A. 

 

Trip delay time adjustment instantaneous to 5 sec divided in 2 ranges: inst.

0.5 sec, 0.2

5 sec. 

 

X48: one (1) operating relay (TRIP); X52: two (2) operating relay (TRIP).  

 

Output relay test. 

 

Manual (local or remote) or programmable automatic reset. 

 

Continuous control of wiring connection between the relay and the CT: output relay will be activated if a wiring interruption occurs. 

The wide current range allows easy selection of precise trip current values, in order to maintain the value of the so called contact voltage below 50V, as 

required by the CEI 64-8 standard. 

The  relay, thanks to its internal filtering, is immune to external disturbances. Its function is also guaranteed with alternate sinusoidal and continually 

pulsating differential currents, which are applied abruptly or rising slowly (type A according to IEC 755 Standard). 

 

4. COLLEGAMENTI ELETTRICI 

Per il collegamento seguire lo schema di inserzione (vedere ultima pagina).  Di seguito si descrivono i diversi punti riguardanti le diverse connessioni 

elettriche. 

NOTA: Tutti i collegamenti devono essere tenuti i più corti possibile. La massima lunghezza raccomandata è di 3 metri. 

Alimentazione 

Fra i morsetti 20 e 22 deve essere collegata la tensione di 115 Vac +/-10%, 48...62 Hz; fra i morsetti 20 e 21 deve essere collegata la tensione di 230 

Vac +/-10%, 48...62 Hz, o (a richiesta) 24 – 48 – 110 - 220 V dc 

La sezione minima dei conduttori relativa all’alimentazione ausiliaria deve essere pari a 0.5 mm

2

 

In fase di installazione deve essere prevista la protezione delle connessioni voltmetriche e di quelle di alimentazione ausiliaria tramite fusibili 

rapidi o ultrarapidi con corrente nominale di 1 o 2A, tensione nominale adatta a quella dell’impianto, e potere di interruzione adeguato alla 

corrente di corto-circuito disponibile nel punto di inserzione (normalmente i tipi 10x38, corpo ceramico, tensione nominale 500 o 660V, caratteristica gG 

o FF e potere di interruzione di 100KA sono adatti a questo scopo). 

Collegamento Toroide 

Collegare i morsetti 1 e 2 con i morsetti di uscita del trasformatore toroidale FRER cod. TDC... o TDA... utilizzando un cavo twistato e schermato (tipo 

Belden 9841 o similare) e collegando esclusivamente una sola estremità dello schermo alla terra dell’impianto. 

NOTA: Il percorso dei cavi di collegamento del toroide deve essere separato dai cavi di alta corrente, alta tensione e da cavi che comandano elementi 

induttivi come teleruttori, ecc. Se sono posati nella stessa canalina metallica usare opportuni separatori. 

Collegamento uscita relè 

L' uscita è costituita da un relè  con un contatto di scambio (X48) o da un relè con due contatti in scambio (X52). 

Il relè di intervento (TRIP) commuta quando si è raggiunto il limite di corrente e tempo prefissato per l’intervento o si verifica un guasto del collegamento 

con il toroide (nel caso di X52DS la commutazione dei due contatti è contemporanea). 

NOTA: Utilizzando i contatti per pilotare carichi induttivi (bobine a relè, teleruttori, solenoidi) è necessario limitare la sovratensione che sistematicamente 

si verifica ai capi dell'induttore in corrispondenza di ogni apertura del contatto, inserendo: un gruppo R/C in parallelo all'induttore, se questo lavora in 

alternata, o un diodo in antiparallelo se l'induttore lavora in continua. All'interno il relè è isolato a 4kV tra i contatti e la bobina. 

Ripristino a distanza Collegare un contatto in chiusura ai morsetti RESET per eseguire il reset manuale a distanza. 

4. WIRING CONNECTION 

In order to do all the connections, follow the diagram on the last page. The following points will explain in more detail. 
NOTE: All the connections must be kept as short as possible. The recommended maximum length is 3 meters. 

Power Supply 

The 115 Vac +/-10% 48...62 Hz supply voltage must be connected to terminals 20 – 22; the 230 Vac +/-10% 48...62 Hz supply voltage must be 

connected to terminals 20 – 21 (available on request also 24 – 48 – 110 - 220 Vdc). Wires for power supply must be at least 0.5 mm

2

. 

 

When installing the meters, a protection of the voltage input terminals and of the auxiliary supply terminals must be carried out by means of 

fast or ultrafast fuses with rated current at 1A or 2A, rated voltage suitable to the system voltage, and breaking power adequate to the short 

circuit current available at the connection point (the types 10x38, with ceramic body, rated voltage at 500V or at 660V, gG or FF characteristic and 

breaking power at 100KA are normally suitable for this application). 

CT Connection 

The terminal blocks 1 and 2 should be connected to the measuring windings of the CT FRER code TDC... or TDA... by a twisted and shielded pair cable 

(type Belden 9841 or similar); the shlield must be connected to the system ground at one end only. 

NOTE: The CT wiring should be placed away from high current and voltage conductors or sources of strong magnetic fields, to minimize noise pickup 

and interference on the  relay. If the wires have only one route, separate the wires with some metallic element.  

Output contact connections 

The output consist of one mechanical relay with one changeover contact (X48) or one mechanical relay with two changeover contacts (X52). 

The TRIP relay will activate when the earth leakage current overcome the trip threshold for the specified delay time or CT wiring interruption occurs (in 

X52DS the two relays activate simultaneously). 
NOTE: Using the contacts for control of inductive loads in Vac (coils of relays, contactors, solenoids),  is necessary to limit the over voltage connecting a 

R/C group in parallel to the inductor.   If it works in DC, a diode in anti-parallel should be connected. The internal relays are isolated  4 kV between 

contact and coil. 
Remote Reset It is possible to execute the remote manual reset by a closing contact connected to RESET terminals. 

 

5. FUNZIONAMENTO 

Vengono di seguito spiegati il funzionamento e la programmazione dei parametri di intervento e ripristino dello strumento. 

LED “ON”: (verde) indica la presenza della tensione ausiliaria. 

LED “TRIP”: (rosso) il led “TRIP” acceso indica che la corrente attraverso il toroide ha superato la soglia TRIP impostata per il tempo programmato. I 

corrispondenti relè sono scattati comandando lo sgancio dell’interruttore generale. 

PULSANTE “RESET”: questo pulsante si usa per il ripristino manuale dello strumento da un intervento (se sono state ripristinate le condizioni 

precedenti l’intervento). 

PULSANTE "TEST": Consente di fare una prova di funzionamento del relè di TRIP.  

NOTA: Fare attenzione al carico collegato ai relè di uscita. Premendo il pulsante, trascorso il tempo di ritardo dell'intervento t(S) impostato, i relè 

commuteranno e resteranno commutati finchè non verrà premuto il pulsante "RESET". 

Programmazione del valore della corrente di intervento 

Si sceglie il campo della corrente di intervento desiderata posizionando i primi due microinterruttori (partendo dall’alto): 

 

Entrambi su I

nx0.1: 25mA

250mA 

 

Solo il primo su I

nx1 (il secondo resta posizionato su I

nx0.1): 250mA

2.5A 

 

Solo il secondo su I

nx10 (il primo resta posizionato su I

nx0.1): 2.5A

25A 

Si imposta il valore di corrente agendo sul trimmer I

n(A). 

Programmazione del tempo di ritardo dell’intervento 

Si sceglie il campo del tempo di intervento desiderato posizionando il terzo microinterruttore: 

 

tx1: istantaneo

0.5sec  

 

tx10: 0.2

5sec 

Si imposta il valore del tempo agendo sul trimmer 

t(s) 

Programmazione del modo operativo del contatto 

Posizionando il quarto microinterruttore si può impostare il tipo di sicurezza: ND (normale) o NE (positiva). 

Programmazione del tipo di ripristino 

Il ripristino dello strumento dopo un intervento può avvenire in modo Manuale Automatico. Quando il ripristino è manuale si può effettuare in maniera 

Locale premendo il tasto RESET o in maniera Esterna tramite un pulsante esterno collegato ai morsetti EXT. RESET (87-88). 

NOTA: Il ripristino è possibile solo quando il valore di corrente differenziale rilevato scende al di sotto del valore di corrente impostato. 

Si sceglie il tipo di ripristino posizionando il quinto microinterruttore:    MAN (ripristino manuale) o AUTO (ripristino automatico) 

5. FUNCTIONS 

Operation and setting about Trip, Alarm and Reset are explained as follows. 
LED “ON”: (green) indicates that the instrument is supplied. 

LED “TRIP”: (red) the led “TRIP” turned on shows that the current through the CT has risen above the trip setpoint and the programmed trip time. The 

trip contact has tripped the circuit breaker. 
“RESET” PUSH-BUTTON: this push-button is used to reset from a fault condition. 

"TEST" PUSH-BUTTON: this push-button allows to do the trip contact test. 

NOTE: Be careful to the load connected to the output contact. If pressed, after the set trip delay time t(S), the output contacts will actuate and will stay 

on that position until the "RESET" button is pressed. 

Trip current setting 

The selection of the trip current range is done switching the two above microswitch: 

 

Both on I

nx0.1: 25mA

250mA 

 

The first on I

nx1 (the second remains on I

nx0.1): 250mA

2.5A 

 

The second on I

nx10 (the first remains on I

nx0.1): 2.5A

25A 

Set the trip current by the trimmer I

n(A). 

Trip delay time setting 

The selection of the trip delay time range is done switching the third microswitch: 

 

tx1: istantaneous

0.5sec 

 

tx10: 0.2

5sec 

Set the delay time by the trimmer 

t(s) 

Operating mode on the trip contact 

 

The selection of the safety operating mode of the trip contact is done by switching thr fourth microswitch: ND (normal) or NE (positive). 

 

A

Reviews: