Installation
20
•
If there is 30-amp service to the inverter/charger,
additional 20-amp (15-amp in Canada) circuit breakers
are required between the inverter/charger and the
loads.
Note:
Models 15 S/D and 20 S/D have built in branch
rated circuit breakers.
2. Open the AC wiring compartment by removing the screws
that secure the cover plate.
3. Feed the 3-conductor, AC input wire(s) through the left
strain relief and into the AC wiring compartment. Give
yourself at least 6 inches of wire to work with.
•
If your unit has one AC input, feed one AC input wire
through the strain relief and into the AC wiring com-
partment.
•
If your unit has dual AC inputs, feed one or two AC
input wire(s) through the strain relief and into the AC
wiring compartment.
4. Strip 1/2 inch of insulation off each conductor.
5. Connect each wire to the pigtails:
•
Black to black (hot or line)
•
White to white (neutral)
•
Green or bare copper to AC GROUND STRIP (ground)
Use the provided wire nuts to make the wire connections.
You may also use butt splices (not included) to make the
wire connections.
If your unit has dual AC inputs, and you are using only
one input, connect the wires to AC Input 1. Do not wire
the both AC Input 1 and 2 together.
Strain
Relief
Strain
Relief
AC
INPUT
AC GROUND
STRIP
AC
OUTPUT 1
AC
OUTPUT 2
Example of Single Input/Dual Output Model