![Freedom Won Freedom Lite Business 40/32 HV Installation Manual Download Page 25](http://html1.mh-extra.com/html/freedom-won/freedom-lite-business-40-32-hv/freedom-lite-business-40-32-hv_installation-manual_2329977025.webp)
Freedom Lite Home and Business HV Installation Manual Revision 1
P a g e
25 | 25
inverter in use (baud rate or CAN messages may be for
another inverter brand) or that you have configured the
inverter or system controller correctly.
Check that your CAN Cable is properly made up on the
pin configuration and that the terminations are good.
Contact Freedom Won or your Authorised Distributor
for assistance
8
The charger will not come on
even though there is power on
the AC input of the inverter and
the charger is activated in the
inverter settings
The battery might be full. Try discharging the battery for
a while and observe if the charger then comes on. If not
then the fault finding process is similar to above.
9
The Freedom Lite error light
keeps illuminating after each
reset
If the battery voltage is within limits this should not
ordinarily occur. Contact Freedom Won or an approved
installer for assistance with determining the problem. If
the main breaker does not trip it is not a critical error
and you may continue using the battery while you make
contact for assistance.
10 The pack voltage is within limits,
but the main breaker still trips
seemingly at random
This could be caused by many things but is most likely
because the current draw is exceeding the battery
current limit setting. Measure the current with a tong
tester while drawing your maximum typical load to
determine if you are exceeding the rated current for the
respective Freedom Lite model. If it is not the current
causing the trip it could be a weak cell or extreme
temperature of the surroundings. Both are unlikely. If
the problem persists, contact Freedom Won.