TROUBLESHOOTING TIPS
Perform the Static Operational Check
1. If this check
fails before step 8
the possible problems are:
Power to the system
Bad control module
2. If this check
fails after step 8
the possible problems are:
Wiring between the control module and the metering valve
Bad control module
Bad metering valve.
Check Input Cables
1. Check the cables between the flow sensors and the summing device.
2. Check the cable between the summing device and the control module.
Perform the Operational Check
1. If this check
fails
step 4
(with discharge flow) the possible problems are:
Wiring to the discharge flow sensor
Wiring between the control module and the summing device
Bad discharge flow sensor
Bad summing device
Bad control module
2. If this check
fails
step 6 but passes step 7
the possible problems are:
Wiring to the foam flow sensors
Wiring between the control module and the summing device
Clogged flow sensors
Bad foam flow sensors
Bad summing device
Bad control module
3. If this check
fails step 6 and fails step 7
the possible problems are:
Clogged flow sensors, metering valve, or plumbing
Bad metering valve