Extended Run alarm
Error code flashes: Er
The Extended Run alarm indicates that the SPGC-220 has run for 60 consecutive minutes with no
change in power consumption.
Is there greater
than 85 VAC
across the hook
terminals?
Set the extended run
disable switch SW2 pole 5
to ON.
Measure for voltage across the hook
terminals.
No
Does the application
require the STP to
run at constant flow
rates for at least 60
minutes?
Yes
Yes
Monitor for proper
operation.
Press reset button
No
Determine the source of the hook
signal.
Repair the source of the hook signal
as applicable.
Press the Reset button
on the SPGC-220.
Monitor for proper
operation.
Monitor for proper operation.