15
AC Input Module (ACI)
The ACI is a non-intrinsically safe module that has 12 identical optically isolated AC input
channels that can be used for dispenser hook isolation, vapor processor input, or as generic AC
inputs. Your console can handle a total of 36 AC inputs, up to three AC Input Modules in one
system, or 72 AC Inputs an expansion console and six AC Input Modules.
AC Input Module Specifications
Number of Channels:
12 optically isolated
Input Voltage Rating:
110 – 240 VAC
Input Current:
7 mA RMS
Dispenser Hook Signals
EVO
TM
600 and EVO
TM
6000 consoles allow for the dispenser hook signals from every dispenser
to be wired to the AC Input Module. This provides electrical isolation for each dispenser. When
making the connection for the hook signals to the AC Input Module, refer to the following
diagram and use these guidelines:
• If there are two hooks per dispenser: wire the two hooks from Dispenser 1 to AC input
channels 1 and 2, the hooks from Dispenser 2 to AC channels 3 & 4, etc.
• If there are three hooks per dispenser, then wire the line and neutral of the three hooks of
Dispenser 1 to the input channels 1, 2,3 and so on.
NOTE
: Each channel requires a neutral to operate properly.
AC Input
Module
RUN
ERR
Chan
3
Chan
2
Chan
1
Chan
6
Chan
5
Chan
4
Chan
12
Chan
11
Chan
10
Chan
9
Chan
8
Chan
7
Incoming Dispenser
Hook Signal
Line
Neutral
Line
Neutral
Line
Neutral
Vapor Processor
(optional)
Generic Device
(optional)
Summary of Contents for EVO 600
Page 1: ...EVOTM 600AND EVOTM 6000 AUTOMATICTANK GAUGES INSTALLATION GUIDE ...
Page 37: ...33 Intentionally Blank ...
Page 38: ...Intentionally Blank ...
Page 39: ...Intentionally Blank ...
Page 40: ...s228180033 r1 ...