14
110/240 VAC line power wire connections
Electrical Panel
No. Conductors, Color (Gauge)
Circuit
20 Amp Circuit Breaker 1 Black wire, 14 AWG (2.5 mm²) min.
110/240 VAC Power
Neutral
1 White Wire, 14 AWG (2.5 mm²) min.
Neutral
Ground Bus
1 Green wire, 14 AWG (2.5 mm²) min.
Ground
Ground Bus
1
Green wire, 12 AWG (
4 mm²
) min.
Safety Ground
Nut
Stud: #8 threaded post
Lock Washer
Earth Ground Conductor
Enclosure
Cup Washer
Flat Washer
NOTE:
The installer must connect the earth ground conductor to the most convenient ground
terminal as long as it meets local and national codes. The earth ground conductor must be 12
AWG (4 mm²) or larger.
Relay output wiring (optional)
The Power Supply Module’s two relay outputs can be used to activate an external alarm (TS-RA2).
You can press the button on the Remote Alarm Acknowledge Unit (TS-RK) to silence the alarm.
NOTE:
The TS-RA2, TS-RA1 and TS-RK are not part of the UL certification of your system. For
more information, see the
TS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms Installation Guide
(part number 000-1027).
Emergency generator applications (optional)
The wiring or use of discrete inputs is optional. (Skip this section if you don’t plan to use this
interface.) Discrete inputs may be wired to an EVO
TM
600 or EVO
TM
6000 console with 18 AWG,
type TFFN or THWN wire. You may also use THHN wire in sizes larger than 18 AWG.
Emergency backup power generator run-relay(s) are wired to the discrete input interface
terminals on the console. A run-relay closure will stop a leak test on the associated generator fuel
tank. When the generator run-relay opens (generator stops running), a run report is produced at
the console, which shows the total and hourly fuel consumption rate during the run cycle.
NOTE:
You must use dry run-relay contacts for this interface because the EVO
TM
600 and
EVO
TM
6000 supply is +5 VDC digital logic power at the IN (input) terminals.
NOTE:
It is recommended that you use: IN 1 & GND for Generator 1 /fuel supply Tank #X,
and IN 2 & GND for Generator 2 /fuel supply Tank #Y. The specific fuel tank(s) assigned are
“programmable.” (See "Power Supply Module (PS)" for wiring details.)