background image

QUICKSTART GUIDE

Electrical Installation

3

Power Wiring Connections

Incoming Power Supply

Before connecting power to drive, test incoming voltages as follows:

230V Models:

 The line to line and line to ground voltage must be 190-253V (208-230V ±10%). The line 

to ground voltage must be less than or equal to 253 V. 

460V Models:

 The line to line and line to ground voltage must be 414-506V (460V ±10%). The line to 

ground voltage must be less than or equal to 506 V. 

If line to line voltage exceeds these ratings, the drive cannot be used on the incoming power supply. An 
additional suitably sized transformer will be required to bring the voltages within limits. 

IMPORTANT:

 If line to ground voltage exceeds these ratings, remove Power Board EMC jumpers from J10 

and J11 (four total). This is common in applications supplied by a Corner-Grounded Delta transformer. Refer 
to the NOTICE above.
1.

Incoming Power terminal block.

2. Power Out to Motor terminal block. If the drive is equipped with a dV/dt 

(EMI) filter, this terminal block is pre-wired to the dV/dt filter. The motor 
is wired to the terminal block on the dV/dt filter.

3. J10 Jumper location (two jumpers here).
4. J11 Jumper location (two jumpers here).

Ground Connections

1.

Make sure a service entrance ground rod is properly installed and connected.

2. An input power ground wire from the supply panel must be connected to the drive.
3. A dedicated output ground wire from the drive must be connected to the motor. Motor and ground 

wires must be bundled together.

Contact with hazardous voltage could result in death or serious injury.

Disconnect and lock out all power before installing or servicing equipment.

Connect the motor, the drive, metal plumbing, and all other metal near the motor or cable to the 
power supply ground terminal using wire no smaller than motor cable wires. 

Close any open conduit holes before finishing installation.

Risk of damage to drive

,

 or malfunction can occur.

Power source line to line, and line to ground voltages must be measured before connecting the 
drive. If line to ground voltage exceeds specification, both pins of EMC jumper J10 must be removed 
to prevent damage to the drive. Refer to “Incoming Power Supply” below.

Ensure that the system is properly grounded all the way to the service entrance panel. Improper 
grounding may result in loss of voltage surge protection and interference filtering.

1

2

3

4

Summary of Contents for SubDrive Connect Plus SDCP-CEN0723

Page 1: ... to improper handling installation or environment Install in a location where temperature is within the range of product rating Mount VFD vertically top up for proper heat dissipation Do not mount VFD in direct sunlight or near other heat sources Do not install in corrosive environments Install away from direct sunlight and extreme temperatures or humidity Installation of non approved screening ma...

Page 2: ...AWG 20 to AWG 2 31 in lbs 3 5 Nm AWG 16 to AWG 2 0 50 in lbs 5 5 Nm Risk of damage to VFD or malfunction can occur Follow all wire routing and grounding instructions carefully Inductive currents caused by parallel wiring or close proximity between high voltage and control wiring can cause unexpected behaviors Do not run input power and motor wires in the same conduit Do not run motor wires from mu...

Page 3: ...ck on the dV dt filter 3 J10 Jumper location two jumpers here 4 J11 Jumper location two jumpers here Ground Connections 1 Make sure a service entrance ground rod is properly installed and connected 2 An input power ground wire from the supply panel must be connected to the drive 3 A dedicated output ground wire from the drive must be connected to the motor Motor and ground wires must be bundled to...

Page 4: ...tions marked Ground Red W Yellow V and Black U For drives that include a dV dt filter motor connections are made at the terminal block on the left side of the dV dt filter 3 at right In this case the terminals are marked Ground Red U Yellow V and Black W NOTE Relay terminals accept wire sizes from 12 to 26 AWG and should be tightened to a torque of 3 in lbs 0 35 Nm Do not use power tools to tighte...

Page 5: ...ode 5 PT100 1000 Connector for external RTD temperature sensor I Positive connection for excitation current circuit for two three and four wire PT100 PT1000 RTD sensors V Positive connection for voltage sensing circuit for two three and four wire PT100 PT1000 RTD sensors I V Negative connections for the excitation and voltage sensing circuits for two three and four wire PT100 PT1000 RTD sensors 6 ...

Page 6: ...ms building up pressure in a controlled manner The Pipe Fill feature is disabled when the switch is in the off down position The Pipe Fill feature is enabled when the switch is in the on up position NOTE Additional configuration of the Pipe Fill feature is available in the SubDrive Connect Plus mobile app Analog Output Selection DIP SW1 Position 4 Use this switch AO to select the signal to be repe...

Page 7: ...ressure is set using the adjusting screw on the sensor itself The Sys tem Response screen is displayed next for Pressure Sensor use Sensor Range This is only configurable when the sensor type is transducer This setting scales system operation to the installed transducer The range is 100 to 300 with a default setting of 200 PSI When changing the setting changes in 10 PSI increments Setpoints Drive ...

Page 8: ...and repeat as necessary Deep Set In cases where the pump is set very deep run the system at open discharge to pump the well down and observe carefully that an Underload is detected properly If the system does not trip as it should adjust to a higher sensitivity setting Underload Off Time This setting determines how long the drive will wait before attempting to run after an Underload event The defa...

Page 9: ...running RUN or stopped STOP 3 When using a pressure transducer the system displays the current sys tem pressure in PSI When using a standard pressure sensor the system displays the current motor speed in Hz When running in HAND mode the system displays the keypad frequency setpoint 4 When using a pressure transducer in AUTO mode the motor speed is displayed at the lower left of the screen In HAND ...

Page 10: ...th Connection After installing the SubDrive Plus app use the following procedure to connect to the drive 1 From the Home screen tap Connect New Product 2 On the New Product Wizard screen tap either Scan QR Code or Enter the Bluetooth Key 3 If using the scanning tool center the QR code on the drive in the screen The code is displayed on the VFD display and on a sticker to the right of the display R...

Page 11: ...s replace drive F7 Auto Overheated Drive High ambient temperature Direct sunlight Obstruction of airflow Fan blocked or inoperable ambient above 122 F 50 C direct sunlight Replace fan or relocate drive as necessary Remove debris from fan intake exhaust F9 Manual Internal PCB Fault A fault was found internal to drive Contact Technical Service F12 Auto Overvoltage High line voltage Internal voltage ...

Page 12: ...ation of this equipment requires detailed installation and operation instructions provided in this manual for use with this product Read entire manual before starting installation and operation End User should receive and retain manual for future use Keep safety labels clean and in good condition High voltages capable of causing severe injury or death by electrical shock are present in this unit T...

Reviews: