13
SETUP
SETUP PAGE 2
SETUP PAGE 3
SETUP PAGE 1
Pressure Sensor 20ma
-999.9 PSI
Lead/Lag Pump 1 Pressure Differential from SP
99.9 PSI
Time Delay Bad Sensor System Shutdown
99.9 Secs
If a 4-20 ma pressure transducer is used in this system and it has an upper pressure other than
150 psi, input the upper pressure range of the transducer (in psi) in this input box.
While on the system screen press
Enter a pressure differential off of pressure set point for each lag pump in these fields.
The program will immediately pause pump operation if the transducer reading drops below 3.8 ma.
This prevents run away operation in case of a bad sensor. The user can delay this pause from occurring
by up to 10 seconds by using this field to prevent nuisance shut downs from transient ma readings.
Go to setup page 3 of setup options
Return to setup page 1 of setup options
Setup Page 2 - Lag Pump Differential Setting and Pressure Transducer Setups