- 10 -
14.7
If the hot water temperature is > 70°C, the fitting should be flushed for at least
3 minutes. Trigger the fitting several times for this purpose.
☞
The thermal disinfection process must be recorded (room, tapping point, date, time,
temperature, duration).
14.8
Turn the temperature selector (a) clockwise until it engages.
Caution!
The temperature selector (a) may
not
be turned beyond the stop in an anti-
clockwise direction.
14.9
Test the limit stop.
14.10
Trigger the fitting to drain the remaining hot water.
14.11
Measure the water temperature. The maximum water temperature may not exceed
40°C (see
☞
Once thermal disinfection has been completed, the scald protector does not need to
be reset.
15. Thermal disinfection -automatic-
This fitting offers thermal disinfection to reduce the risk of a legionella infection.
Caution!
The directions in the Thermal Disinfection Planning Aid (01805618) must be
adhered to.
Warning!
Personal protective measures (scald protection) must be implemented for the
duration of the thermal disinfection. This might include cordoning off the shower
facilities.
Failure to observe this instruction can result in injuries due to scalding.
The operator is responsible for the execution, monitoring, and logging (room,
tapping point, date, time, temperature and duration).
The manufacturer does not accept any liability for claims by third parties relating to
the improper execution of thermal disinfection on the part of the operator.
☞
At the factory, the thermal disinfection function is set so that the fitting cools down for
1 minute after a 5 minute application time.
☞
Thermal disinfection can only be triggered using the remote control.
You can adjust the thermal disinfection parameters using the remote control (not
part of the scope of delivery, see
).