background image

2.5. Chimney connector

-

The connection to flue must be carried out
according to local building regulations.

-

The appliance must be installed as close as possible
to the chimney.

-

The connector pipe must be approved for installation
with combustion products (either 24 ga. Black painted
or blued steel or 316 grade 20 ga. Stainless steel or 1
mm vitreous enamelled steel).

-

Pipe diameter must not be less than the appliance
spigot diameter. If there is no other solution, the
reduction can not be more than one diameter lower
than the flue spigot and be situated as distant as
possible from the flue connection of the appliance.

-

The connection can be either vertical or horizontal. For
horizontal connections, avoid right angle bends.

-

The join between the connection pipe and the
stovepipe, and the flue, must be leak tight.

-

For the premises equipped with a mechanical
controlled ventilation, the airtightness has to prevent
the exhauster drawing out the smokes from the
exhaust gas pipe.

-

The connection pipe and any draught stabiliser must
have access for cleaning.

-

The spigot should be connected to a minimum of 125
mm flue system and in that case the appliance is
capable of burning untreated wood and recommended
solid fuels.

2.6. Pre-utilisation check

Check the condition of the filler seals, that the door
closes correctly, that the window is not damaged, that
the smoke passages are not obstructed by pieces of
packaging or removable parts. All removable parts, fuel
retainer, oscillating grate, baffle, must be correctly
installed.

Note :

if it acts of a ceramics braid, it is consumable and

thus brought to be changed by the user.

2.7. Door closing pressure

Figure 6

The closing latch rotates around a pressure screw
positioned cam.

-

Loosen pressure screw

1

,

-

Turn cam to desired position.

2

,

-

Tighten pressure screw

1

.

2.8. Maintenance of the Chimney

Very important :

In order to avoid any incident

(chimney fire, etc...), maintenance tasks must be
carried out regularly. If the appliance is regularly used,
the chimney should be swept several times per year,
together with the stovepipe connection section.

If the chimney catches fire, you must cut off the flue
draught, close the doors and windows, hatches and
keys,

remove the embers from the stove

DQGFDOO

the Fire

%ULJDGHZLWKRXWGHOD\

DO NOT OPEN THE DOOR OF THE APPLIANCE
(OR AIR INLET) UNDER ANY CIRCUMSTANCES

Chimney condition should be checked at least once per
year by a professional engineer.

6

Technical manual “1171”

“MONTFORT” - ref. 134 05 01

Installation instructions

 

Figure 6 - Adjusting of the door closing pressure

1

Pressure screw

2

Cam

Summary of Contents for MONTFORT 134 05 01

Page 1: ...s Spare parts Warranty certificate Document n 1171 20 02 2013 MONTFORT Wood stove EN 13240 Model 134 05 01 Output 5 kW Technical manual to be saved by the user for future reference FR EN NL IT Parc d...

Page 2: ...ith wood p 8 Instructions for use with solid fuel p 8 Cleaning p 9 Maintenance of the Chimney p 9 Maintenance of the stove p 9 Recommendations p 9 Firebricks p 9 Trouble Shooting p 10 Spare parts p 11...

Page 3: ...61 Co 13 O2 0 13 Smoke temperature C 304 Fuel rate kg h 0 6 The performances indicated opposite result from tests carried out in accordance with standard EN13240 with logs of 12 of 30 cm and a depress...

Page 4: ...ise it must necessary to install a non combustible protection There must be a clearance of at least 150 mm at each side of the appliance and at the back of the appliance from a non combustible wall Th...

Page 5: ...embers It must permit an easy sweeping 2 4 Assembly of flue collar The stove is supplied with a connection flue spigot with an inner diameter of 125 mm and an outer diameter of 139 mm 2 4 1 Smoke exit...

Page 6: ...d wood and recommended solid fuels 2 6 Pre utilisation check Check the condition of the filler seals that the door closes correctly that the window is not damaged that the smoke passages are not obstr...

Page 7: ...an if required Do not attempt to relight the fire until the cause of the fume emission has been identified and corrected If necessary seek expert advice Note It is recommended to use a fireguard in th...

Page 8: ...to the right Open the primary air inlet C1 Lay firelighters or rolled up newspapers on the grate with a reasonable quantity if necessary of dry kindling wood Place a small quantity of solid fuel on to...

Page 9: ...of the stove The appliance must be cleaned regularly together with the connecting pipe and the flue pipe Remove all deposits from the combustion chamber and clean the grate area Cleaning of the glass...

Page 10: ...n lighting up Flue duct is cold Burn paper and kindling wood to increase heat Room is in decompression negative pressure In houses equipped with mechanical ventilation partly open a window until the f...

Page 11: ...ng plate A B C D E F G 01 18 259015 00 Fixing plate A B C D E F G 04 19 262612 00 Heat shield A B C D E F G 01 20 270412 00 Air control flap A B C D E F G 01 21 300118 MK Leg D 04 21 300118 MP Leg E 0...

Page 12: ...12 Technical manual 1171 MONTFORT ref 134 05 01 Spare parts Figure 10 Stove exploded view 3 45 45...

Page 13: ...04 EF Reducing plate A B C D E F G 02 36 327906 MK Ash pan guide D 01 36 327906 MP Ash pan guide E 01 36 327906 RH Ash pan guide F 01 36 327906 RP Ash pan guide G 01 36 327906 EF Ash pan guide A 01 36...

Page 14: ...parts covered by the guarantee is found to be too costly vis vis the price of the appliance the decision to replace or repair the appliance will be taken by the vendor Our guarantee is for 2 two year...

Reviews: