2.7 Chimney connector

The connection to flue must be carried out according to
local building regulations.

The appliance must be installed as close as possible to
the chimney.

The connector pipe must be approved for installation
with combustion products (either 24 ga. Black painted
or blued steel or 316 grade 20 ga. Stainless steel or 1
mm vitreous enamelled steel).

Pipe diameter must not be less than the appliance
spigot diameter. If there is no other solution, the
reduction can not be more than one diameter lower
than the flue spigot and be situated as distant as
possible from the flue connection of the appliance.

The connection can be either vertical or horizontal. For
horizontal connections, avoid right angle bends.

The join between the connection pipe and the
stovepipe, and the flue, must be leak tight.

For the premises equipped with a mechanical
controlled ventilation, the airtightness has to prevent
the exhauster drawing out the smokes from the
exhaust gas pipe.

The connection pipe and any draught stabiliser must
have access for cleaning.

The spigot should be connected to a minimum of
125 mm flue system and in that case the appliance is
capable of burning untreated wood and recommended
solid fuels.

2.8 Pre-utilisation check

-

Check that the seals of the smoke-line are in good
condition. Check that the door closes correctly. Check
that the glass is not damaged. Check that the smoke
passages are not obstructed by packaging or
removable parts. Check that all removable parts are
correctly installed.

Note :

if it acts of a ceramics braid, it is consumable and

thus brought to be changed by the user.

2.9 Maintenance of the Chimney

Very important :

In order to avoid any incident

(chimney fire, etc...), maintenance tasks must be
carried out regularly. If the appliance is regularly used,
the chimney should be swept several times per year,
together with the stovepipe connection section.

If the chimney catches fire, you must cut off the flue
draught, close the doors and windows, hatches and
keys and call the Fire Brigade without delay.

DO NOT OPEN THE DOOR OF THE APPLIANCE
(OR AIR INLET) UNDER ANY CIRCUMSTANCES

Chimney condition should be checked at least once per
year by a professional enginee

6

Technical manual “1274”

“SAVOY MK2” - model : 134 08 09

Installation instruction

A

1

2

3

4

1

1

3

6

4

5

1

- Chimney

2

- Funnel-shape fireproof

material.

3

- Non-combustible plate

4

- Access to cleaning

5

- Insulation

6

- Plate not removable and

ventilated air.

Summary of Contents for SAVOY MK2 134 08 09

Page 1: ...Output wood 8 kW Output coal 7 kW Technical manual to be saved by the user for future reference STAUB FONDERIE SARL with the capital of 6 359 540 Head Office Address 2 rue Saint Gilles 68230 TURCKHEIM...

Page 2: ...e shooting p 9 Spare parts p 10 FRANCO BELGE congratulates you on your choice FRANCO BELGE guarantees the quality of its appliances and is committed to meet its customers needs FRANCO BELGE which can...

Page 3: ...12 Nominal heat output kW 7 2 Efficiency 71 9 Co 13 O2 0 13 1 3 Appliance description Wood stove in conformity with DIN EN 13240 2005 10 Intermittent burning heating appliance Detachable flue spigot f...

Page 4: ...tible material as per the Building regulations Otherwise it must necessary to install a non combustible protection There must be a clearance of at least 150 mm at each side of the appliance and at the...

Page 5: ...diameter of 139 mm The stove is set from the factory with a top outlet 2 5 Top flue outlet Figure 3 First remove the flue baffle A The stove is set from the factory with a top outlet Do not remove the...

Page 6: ...ss for cleaning The spigot should be connected to a minimum of 125 mm flue system and in that case the appliance is capable of burning untreated wood and recommended solid fuels 2 8 Pre utilisation ch...

Page 7: ...not an incinerator Use hard wood logs which have been cut for at least two years and stored under a ventilated shelter Use hardwood that have a higher calorific value per cu metre Yoke elm oak ash ma...

Page 8: ...pliance is cold Remove the ash drawer using the tool provided Empty the ashes carefully with regard to the live embers 3 5 Maintenance of the Chimney Very important In order to avoid any incident chim...

Page 9: ...mall wood sticks bundles carpentry offcuts plywood pallets etc Smokes when lighting up The flue damper is closed Open the flue damper Flue duct is cold Burn paper and kindling wood to increase heat Ro...

Page 10: ...ic glass 402 x 322 01 17 189103 Screw 27x8x6 02 18 189104 Screw 6x22 02 19 189825 Screw M5x6 01 20 205362 Back panel 01 21 222581 Flue baffle 01 22 236138 Reducing plate 01 23 237406 Reducing plate 01...

Page 11: ...3 2 1 4 1 4 3 8 4 5 2 1 2 0 3 4 6 7 3 3 4 0 8 4 6 4 1 4 1 3 4 2 1 3 3 9 2 7 4 4 2 3 1 2 3 6 1 7 2 4 2 2 5 3 7 1 4 3 2 5 1 0 1 6 9 1 5 1 8 1 0 2 5 1 0 2 5 2 5 1 0 1 9 3 1 4 2 1 4 3 5 3 0 1 7 1 8 2 9 2...

Page 12: ...he exception of closed combustion fireplace and inserts for which our guarantee is 5 five years excluding the following 1 Indicator lights fuses electrical elements and fans 2 Parts subject to wear or...

Reviews: