Montfort MK2 EA - 1340502
6
Technical manual "1300"
1 diameter lower than the flue spigot and be situated
as distant as possible from the flue connection of the
appliance.
- The connection can be either vertical or horizontal.
For horizontal connections, avoid right angle bends.
- The join between the connection pipe and the
stovepipe, and the flue, must be leak tight.
- For the premises equipped with a mechanical
controlled ventilation, the airtightness has to prevent
the exhauster drawing out the smokes from the
exhaust gas pipe.
- The connection pipe and any draught stabiliser must
have access for cleaning.
- The spigot should be connected to a minimum of
125 mm flue system and in that case the appliance is
capable of burning untreated wood.
2.8. Pre-utilisation check
Check the condition of the door rope seals. Check the
door closes correctly ans that the glass is not damaged.
Ensure that all internal packaging materials have been
removed and are not blocking any of the air passages.
Check that all removable internal components are
correctly installed as they May have moved in transit.
Note : all gaskets glass fiber ropes, seals, are
consumable parts and must be changed on a regular
basis by the user.
2.9. Door closing pressure
(
Figure 4)
The closing latch rotates around a pressure screw
positioned cam.
- Loosen pressure screw 1,
- Turn cam to desired position. 2,
- Tighten pressure screw 1.
2.10. Maintenance of the Chimney
Very important : To avoid accidents (chimney fire,
etc.), regular maintenance should be carried out.
If the stove is regularly used, the chimney should
be swept several times per year, together with the
stovepipe connection section.
If the chimney catches fire, you must cut off
the flue draught, close the doors and windows,
hatches and keys and call the Fire Brigade
without delay.
DO NOT OPEN THE DOOR OF THE APPLIANCE
(OR AIR INLET) UNDER ANY CIRCUMSTANCES.
Chimney condition should be checked at least
once per year by a professional engineer.
2.11. Removing and replacing the flue
baffle
(figure 5)
- Open the front door
- Remove the ash-pan
- Remove the fuel retainer
- Remove the firebrick
(fig. 5a)
- Remove the firebrick (fig. 5b)
- Remove the grate (fig. 5c)
- Remove the flue baffle (fig. 5d)
If necessary, change the 2 gaskets
(see p. 12 n° 6)
and replace the flue baffle in the reverse order.
1 - Pressure screw
2 - Cam
2
1
- Figure 4 - Ajusting of the door closing pressure