Technical data
Operating Manual EM-PQ 2300
9
Impact resistance IK06 as per EN 61010-1:2011-07, 8.2.2
Service life
At +25 °C ambient temperature 10 years,
at +40 °C ambient temperature 6 years
EMC
EMC as per EN 61326-1
EN 61000-4-2, electrostatic discharge: air 8 kV and contact 4 kV with
horizontal and vertical coupling plane
EN 61000-4-3, radiated immunity (EMS) 80 MHz
– 1 GHz, horizontal
and vertical, level 10 V/m = industrial environment radiation, Class A
EN 55022A EMI 30 MHz
– 1 GHz = office and residential area,
Class B
EN 61000-4-6, immunity to conducted disturbances, level 10 V RMS,
150 kHz
– 80 MHz
EN 61000-4-4, burst immunity, 1 kV capacitive coupling, 2 kV
injection into power supply cable and voltage measurement inputs
EN 61000-4-5 surge immunity, 2 kV injection into power supply cable
and voltage measurement inputs
Ambient conditions
Temperature range
-20 °C to +60 °C, noncondensing
Installation altitude
Maximum height above sea level 2000 m
Measuring system
Accuracy
Averaging function
Harmonics measurement
Interharmonics
Harmonics
At 25 °C ambient temperature, voltage and current readings
1%,
temperature readings
2 °C
L1, L2, L3, L1
–L2, L2–L3, L3–L1, N, PE: over 200 ms
Measured from L1
–L3, not from N, PE
Measured down to 5 Hz
Up to the 51st harmonic