background image

5

E33 FPI Direct Vent Gas Insert

REQUIREMENTS 

5.08: 

Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements: 

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for 
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than 
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall 
be satisfied:  

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is 
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery 
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure 
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of 
qualified licensed professionals for the installation of hard wired carbon monoxide detectors 

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon 
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of 
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed. 

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions 
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.  

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The 
sign shall read, in print size no less than one-half (1/2) inch in size, 

"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL 

OBSTRUCTIONS". 

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation 
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 
5.08(2)(a)1 through 4.  

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by 
the Board; and  

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or 
structure used in whole or in part for residential purposes.  

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product 
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the 
instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 

1. Detailed instructions for the installation of the venting system design or the venting system components; and 

2. A complete parts list for the venting system design or venting system.  

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a 
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies 
"special venting systems", the following requirements shall be satisfied by the manufacturer: 

1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and  

2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 
detailed installation instructions.  

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, 
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of 
the installation.  

MA Code - CO Detector

(for the State of Massachusetts only)

Summary of Contents for E33-LP1

Page 1: ...tallation and service must be performed by an authorized installer service agency or the gas supplier FOR YOUR SAFETY What to do if you smell gas Do not try to light any appliance Do not touch any ele...

Page 2: ...ch The E33 NG1 and E33 LP1 have been approved by Warnock Hersey for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many troub...

Page 3: ...CO Detector for the State of Massachusetts only 5 INSTALLATION Important Message 6 For Your Safety 6 Gas Pressure Testing 6 Specifications 6 Installation Into A Solid Fuel Burning Fireplace or Factor...

Page 4: ...local codes if any If none follow the National Fuel Code ANSI Z223 1 NFPA 54 or Natural Gas and Propane Installation Codes CSA B149 1 This vented gas fireplace heater is not for use with air filters D...

Page 5: ...in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY...

Page 6: ...been installed The fireplace and fireplace chimney must be clean and in good working order and constructed of non combustible materials and chimney cleanouts must fit properly Refractory glassdoors s...

Page 7: ...rnia to cause cancer birth defects or other reproductive harm a Brick Panels b Log Installation c Faceplate Trim d Standard Flush Door e Flush Louvers f Full Screen Doors g Excalibur Surround h Excali...

Page 8: ...Alcove side wall must have a min of 8 clearance on one side COMBUSTIBLE MANTEL CLEARANCES Because of the extreme heat this fireplace emits the mantel clear ances are critical Note Anon combustible man...

Page 9: ...rough the chimney above the appliance Movetheapplianceintotheexact location where it is to be installed Ensure that the Insert is level In areas of consistently high winds we recommend using the Simps...

Page 10: ...he pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label 6 When finished reading manometer turn off the gas valve disconn...

Page 11: ...ket 5 Place the top bracket onto the top edge of the top panel refer to Diagram 2 Diagram 2 6 Slide the top panel and bracket assembly carefully onto the baffle plate ensuring the panel is centered Ma...

Page 12: ...do not force them into position to avoid chipping 3 Remove the grate by removing the two Phillips screws Slide the grate outwards to remove it from the unit refer to Diagram 1 Diagram 1 2 Remove the...

Page 13: ...into position until it touches the locating tab see Diagram 6 7 Locating Tab 03 20 Locating Pin Diagram 6 Diagram 7 03 23 03 20 03 17 03 21 9 Place log 03 22 over log 03 23 and log 03 20 Ensure the pi...

Page 14: ...4 lines up with the right pin of log 03 23 and the right pin of log 03 21 refer to Diagram 11 03 24 03 23 03 21 Locating Pins Diagram 11 12 Place log 03 19 over the left center of the grate Ensure the...

Page 15: ...llation section in E33 Manual Ensure you slide the bottom log 03 17 off to the right hand side to avoid chipping 5 Remove burner by unscrewing the 2 screws 6 Pull off the pilot cap to expose the pilot...

Page 16: ...cordance with the authority having jurisdiction If the information in these instruc tion is not followed exactly a fire explosion or production of car bon monoxide may result caus ing property damage...

Page 17: ...anging the battery Installer Notice These instructions must be left with the appliance 41 Check for gas leaks with a proper soapy solution or leak detector 42 Check for proper spark between the ignito...

Page 18: ...4 and do a trial fit to the unit Make any necessary adjustments and when it fits properly then tighten down the screws Diagram 3 7 Tuck the wires into the faceplate to keep them away from the insert...

Page 19: ...ceplate as shown Fan Rheostat 3 Secure loose wires using wire clips along the back of the left side of the faceplate Ensure to run the wires away from the firebox as much as possible 4 Align the facep...

Page 20: ...over top of the glass door push in the bottom of the door frame to secure in place NOTE To ensure the gap between the door frame and faceplate legs are equal approximately 1 2 on each side you may ne...

Page 21: ...rthehinge Flip hinge over the Bottom Louver and secure using 3 screws Bottom Louver Hinge Location 1 The top louver is held in place by friction fit Refer to Diagram 1 Diagram 1 4 Install the Top Fram...

Page 22: ...Doors by placing over top of the hinges on the faceplate Hold the door at a 45 degree angle to avoid scratching the faceplate 8 Close screen doors Hinge Screen Door 3 Hold the Faceplate Trim up again...

Page 23: ...plit lock washer and then the nut and tighten DOUBLE DOOR OPTION Remove the handles by removing the nut andscrew Installthenewhandlesbyplacing theminpositionovertheholesonthedoor s Put the studs throu...

Page 24: ...g plug for your protection against shock hazard and should be plugged directly into a properly groundedthree prongreceptacle Donotcutorremove the grounding prong from this plug Caution Ensure that the...

Page 25: ...n the wall Switch the remote receiver to remote mode The remote control is now ready for operation OPTIONAL REMOTE CONTROL OPTIONAL WALL THERMOSTAT A wall thermostat may be installed if desired follow...

Page 26: ...disappear in a few minutes as the glass heats up DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE OPERATING INSTRUCTIONS 1 Read and understand these instructions before operating this applia...

Page 27: ...N This sound will increase or decrease in volume depending on the speed setting of your fan speed control Burner Tray The burner tray is positioned directly under the burnertube s andlogsandismadeofad...

Page 28: ...his condensation and fog is normal and will disappear in a few minutes as the glass heats up Never operate the appliance without the glass properly secured in place or with the door open 7 Donotusethi...

Page 29: ...pliance with glass panels removed cracked or broken Replacement of the glass should be done by a licensed or qualified service person Flush Glass Replacement Remove the flush door front refer to the S...

Page 30: ...fan 15 Reverse above steps Sealfanaccesspanelusinghightemperature silicone sparingly 13 Pull Fan Assembly forward to disengage the fan clip on the rear wall Then lift the Fan Assembly up and pull thro...

Page 31: ...19 Grommet for Power Cord 340 924 Flush Louvers Set Black Gold 340 922 Flush Louvers Set Black 340 926 Flush Louvers Set Black Steel 21 Top Flush Louver 23 Bottom Flush Louver 340 901 Brick Panel Set...

Page 32: ...T Natural Gas Propane 59 Valve Tray 910 034 Pilot Assy 3 Flame Conv NG 66 910 038 Pilot Assy 3 Flame S I T NG 910 039 Pilot Assy 3 Flame S I T LP 67 904 690 Orifice 31 NG 904 641 Orifice 50 LP 936 170...

Page 33: ...8 88 89 90 90 FULL SCREEN FRONT Part Description PARTS LIST 83 Top Frame 84 340 910 Full Screen Door Black 85 Full Screen Left Door 86 Full Screen Right Door 87 Bottom Frame 88 Screw 8 x 1 2 Self Tapp...

Page 34: ...lack 94 Trim Side Right 95 Trim Top 96 Trim Side Left Assy 97 910 246 Burner ON OFF Switch 98 910 330 Fan Speed Control 120 V 99 Faceplate Filler 172 320 940 Hearth Trim 1 176 320 942 Hearth Trim 2 18...

Page 35: ...AME Part Description 341 914 Contemporary Faceplate Door Frame 90 Complete Faceplate 91 Door Frame 92 Bottom Louver 93 Hinges 910 246 Burner ON OFF Switch 910 330 Fan Speed Control 120V 904 569 Fan Sp...

Page 36: ..._______________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ____________________________...

Page 37: ..._______________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ____________________________...

Page 38: ..._______________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ____________________________...

Page 39: ...portation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within three days of...

Page 40: ...__________ Printed in Canada FPI fireplace products are designed with reliability and simplicityinmind Inaddition ourinternalQualityAssurance Teamcarefullyinspectseachunitthoroughlybeforeitleaves our...

Reviews: