Part No. 26120 Rev. G August 2018
- 32 -
Inline 4000 Series Cabinets
Controller Settings
REFRIGERATED CABINETS
-
SPECIFICATIONS
Dixell XR40CX Settings
Cold Models
Controlled Ambient
Models
Parameter
Integral
Condenser
Remote
Condenser
Integral
Condenser
Remote
Condenser
Units / Range
Set Point
Set
2
2
16
16
degC
Differential
Hy
2
2
2
2
degC
Third Probe Used
P3P
Y
n
Y
n
n, Y
Anti Short Cycle Delay
AC
0
0
0
0
Min
Comp On Time - Faulty Probe
C0n
4
4
4
4
Min
Comp Off Time - Faulty Probe
C0F
6
6
6
6
Min
Defrost Terminate Temp
dtE
3
3
3
3
degC
Interval Between Defrosts
IdF
4
4
4
4
Hrs
Display During Defrost
dFd
DEF
DEF
DEF
DEF
rt, it, SEt, DEF
Maximum Temperature Alarm
ALU
12
12
110
110
degC
Differential For Temp Alarm
AFH
8
8
1
1
degC
Temperature Alarm Delay
Ald
60
60
15
15
Min
Probe For High Temp Alarm
AP2
P3
nP
P3
nP
nP, P1, P2, P3, P4
High Temp Alarm Set Point
AU2
100
110
100
110
degC
High Discharge Temp Alarm Diff
AH2
25
5
25
5
degC
High Discharge Temp Alarm delay
Ad2
0
15
0
15
Min
High Alarm Delay At Start
dA2
0
1.3
0
1.3
Min
Comp Off For High Temp Alarm
AC2
Y
n
Y
n
n. Y
Parameters shown thus are Dixell default settings