FP S-ENGuard Model series W640 / W667
22
Step 6:
Connecting to the power supply
Danger to life through electric shock!
There is danger to life when touching live parts.
Disconnect the cables to which the device is connected from
the power supply and secure them against being switched on
again.
Check that the cables to which the device is connected are
voltage-free.
Do not connect the power supply until all other installation
work has been completed.
Danger to life through electric shock when operating on an
unsuitable electrical system!
Only connect the device to an electrical system that meets
the following requirements:
– Fuse protection with a circuit breaker of type max. 10 A,
characteristic B, switching capacity 6 kA.
– Disconnecting device two-pole (L, N), with a minimum
contact distance of 3 mm.
Damage to the device due to incorrect voltage connection!
Make sure that the cable is connected correctly.
Make sure that the characteristic values U = 100 - 240 V are
observed.
Inadequate power supply due to insufficient cable cross
section!
Only use cables with sufficient wire cross-section for connec-
tion.
Damage to the connection terminals due to excessive
torque!
Use a torque screwdriver.
Tighten the clamping screws to a torque of 0.5 - 0.6 Nm.