Page 14 of 49
Ceiling cassette Fan Coil Unit, 4-pipe system
Model: FP-KM
THE INSTALLATION MANUAL
HOT & CHILLED WATER SYSTEM AIR CONDITIONERS
First check the contents of the package.
FACTORY SUPPLIED ACCESSORIES
Check to ensure all factory supplied accessories are supplied with the unit.
The appliance should be Installed In accordance with national wiring regulation.
SAFETY CONSIDERATIONS
•
When working on air conditioning equipment, observe precautions in this manual, and on plates and tables
attached to the unit. Follow all safety codes and other safety precautions that may apply.
•
Installing and servicing air conditioning equipment should be done by trained and qualified service personnel
only. Untrained personnel can perform only basic maintenance functions such as cleaning coils, filters and
replacing filters.
•
Ensure that the electrical supply and frequency are adequate for the operating current required for this
specific installation.
•
The manufacturer denies any responsibility and warranty shall be void if these installation instructions are not
observed.
•
Never switch off the power main supply when unit is operating in the cooling cycle.
To switch off the fan coil unit use only the ON-OFF button.
•
This avoids over-flow in the drain pan, by allowing the pump to drain any condensate water due to regulating
valve losses when chiller is working.
WARNING:
Before any service or maintenance operations turn off the main power switch.
OPERATING LIMITS
•
Power supply
Volt
Phase
Hz
230
1
50
•
Water circuit
-
Minimum entering water temperature: +2 °C
-
Maximum entering water temperature: +70 °C
-
Water side maximum pressure: 1600 kPa
FACTORY SUPPLIED ACCESSORIES
AMOUNT
LCD Remote control
1
Installation manual
1
Batteries
2
External drain pan
1