background image

2- 

year

warranty

Ajustes 05_19_2017

User Manual

 Uninterruptible Power Supply System 

FDC-2012R-I / FDC-3012R-I

Summary of Contents for FDC-2012R-I

Page 1: ...2 y e a r w a r r a n t y Ajustes 05_19_2017 User Manual Uninterruptible Power Supply System FDC 2012R I FDC 3012R I ...

Page 2: ...ertified electrical cables for input and output connections During the installation of this equipment make sure that the sum of the leakage currents of the UPS and the connected loads shall not exceed 3 5 mA CAUTION The unit is heavy Lifting the unit requires a minimum of two people 1 4 Important safety instructions Do not disconnect the mains cable on the UPS system or the building wiring outlet ...

Page 3: ...e of damage be found or if some parts are missing do not turn the UPS on you must immediately notify the carrier or dealer where you purchased the unit 2 2 UPS diagram Front view Rear view FDC 2012R I FDC 3012R I 1 Programmable outlets for non critical loads 2 Dedicated outlets for critical loads 3 AC input 4 Modem phone network surge protection 5 USB communication port 6 RS 232 communication port...

Page 4: ...tep 3 Verify that the UPS is stable and firmly attached to the base Intelligent slot RS 232 port USB port To allow for unattended UPS shutdown start up and status monitoring connect one end of the communication cable to the USB RS 232 port and the other end to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor its status thro...

Page 5: ...nter button Select button ON Mute Select button Turn on the UPS Press and hold the ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm When the UPS is on battery mode press and hold this button for at least 3 seconds to disable or enable the alarm system This command would not apply when warnings or errors occur Up key Press this button to display previous selection in the UPS ...

Page 6: ...oltage output voltage and output frequency V voltage Hz frequency Indicates that the programmable management outlets are working Indicates that the UPS is connected to utility power Indicates that the battery is working Indicates the charging status Indicates the UPS is working in bypass mode Indicates the UPS is working in ECO mode Indicates the UPS is working in converter mode Battery level indi...

Page 7: ... 50 The output frequency is set to 50Hz CF 60 The output frequency is set to 60Hz Parameter 2 Activates or cancels the ECO mode Two options are available ENA ECO mode enable DIS ECO mode disable Default Parameter 2 Use this menu to set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode For 200 208 220 230 240 VAC mo...

Page 8: ...feature ENA Programmable outlets enabled DIS Programmable outlets disabled Default 10 Backup time setting for programmable outlets Interface Setting Parameter 2 Sets the backup time limits for the programmable outlets 0 999 Use this setting to define the programmable outlets backup time in minutes from 0 999 in order to connect non critical devices on battery mode Default 999 12 Battery total Ah s...

Page 9: ...he connection of an external output isolation transformer ENA If selected the UPS will be allowed to connect to an external output isolation transformer DIS If selected the UPS will be denied to connect to external output isolation transformer Default 18 Runtime setting display Interface Setting Parameter 2 Use this setting to configure the runtime on the display EAT If EAT is selected it will sho...

Page 10: ...in acceptable range the UPS will supply pure and stable AC power to connected loads The UPS will also charge the battery while in online mode ECO mode Efficiency Corrective Optimizer Frequency converter mode Energy saving mode When the input voltage is within the voltage regulation range the UPS will bypass voltage to loads for energy saving The UPS will also charge the battery while in ECO mode W...

Page 11: ... beeping every second Fault code 49 becomes illuminated and the alarm starts beeping continuously Fault code 43 becomes illuminated along with the icon on the LCD display and the alarm starts beeping continuously Battery backup time is shorter than its nominal value Charge the batteries for at least 5 hours and then check their capacity If the problem persists consult your dealer Batteries are not...

Page 12: ...gement software Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Dimensions Weight Cord length Additional information Warranty 2000VA 2000W 3000VA 3000W Double conversion 200 240VAC 175VAC 155VAC 135VAC 125VAC 3 based on load percentage 100 80 80 70 70 60 60 0 Low line transfer voltage 10V 300VAC 3 High line transfer volta...

Page 13: ......

Reviews: