background image

MIMO2+, Multiple Input 

– Multiple Output 

Module Technical Appendix

                                                                          

 

 
 

                         1080 Centre Rd.  Ste C 

Auburn Hills, MI 48326   

www.fortrezz.com

 

Phone: (248) 481-7092 

         

[email protected]

         

                                     Made in USA        

072916 

Input-to-Relay Mapping 

MIMO2+ or MIMO3 can be configured to automatically turn a relay on/off when an input or several inputs trigger or untrigger.  
The Configuration Command Class, Parameters 1 and 2, is used to set this mapping for REL1 and REL2, respectively.  When this 
mapping  is  enabled,  Z-Wave

TM

  commands  to  set  a  relay  are  ignored  or  overridden  and  the  relay  state  is  determined  by  the 

hardware.  The default for each relay is no input-to-relay mappings. 

Each Relay mapping can be a logical (AND/OR) combination of the MIMO2+ inputs.  Configuration Command Class parameters 1 
and 2 are shown in the following diagrams.  Note that for each parameter, bits 0-4 settings are not shown below, but  are the 
momentary  latch  count  as  described  in  the  Configuration  Command  Class  section  above.    
These  parameters  are  one-byte 
parameters (as are all Configuration Command Class parameters).  

 

 

EXAMPLES (where SIGx represents the input trigger state):  

1) If all the bits are set for the REL1 configuration, then the mapping equation is: 

REL1 state = (SIG1 AND SIG2) OR SIG1 OR SIG2 

 

REL1 is set if SIG1 is triggered or if SIG2 is triggered; cleared otherwise 

2) If only bit 7 is set for the REL2 configuration, then the mapping equation is: 

REL2 state = SIG1 AND SIG2 

 

REL2 is set if SIG1 and SIG2 are both triggered; cleared otherwise 

3) If only bit 5 is set for the Relay 1 configuration, then the mapping equation is: 

REL1 state = SIG1 

 

REL1 is set if SIG1 is triggered, cleared otherwise 

 

POWER DROPOUT    

A periodic Power Dropout status blink (see above indication table) is shown if the supplied power drops below approx. 11.5 Volts.  
In addition, the MIMO2+ implements the Alarm Command Class (Version 2), which provides for a ‘power dropout’ alarm report 
to be sent when the supplied power drops.   By default, this report is enabled and sent to Node 1 (assumed to be the controller).  
It can be disabled or enabled by the command ALARM_SET_V2.  The node sending the ALARM_SET_V2 command is the node to 
which the  MIMO2+ sends the alarm report.  After a power dropout alarm event, the  MIMO2+ sends a ‘power applied’ alarm 
report when the supplied power rises above approx. 12 Volts.  Also, during the power dropout, input signal triggering is not active. 

For sending the alarm signal, the MIMO2+ relies on residual power in the MIMO2+ circuitry when power completely drops out.  
Typically, this will be sufficient to perform this action.  

7 6 5 4 3 2 1 0

SIG1

SIG2

SIG1 AND SIG2

OR

Parameter 1: REL1

Parameter 2: REL2

7 6 5 4 3 2 1 0

SIG1

SIG2

SIG1 AND SIG2

OR

Summary of Contents for MIMO2+

Page 1: ...ge to the unit and may cause damage to property and or personal injury including loss of life o WARNING Do not attempt to use the relays to switch residential or industrial Alternating Current AC lines The relays are to be used for low power load control only Refer to above electrical specifications for relays Do not store highly flammable items such as oily rags or other combustibles near your MI...

Page 2: ...ically activated by Z WaveTM commands However the user can override Z WaveTM control by configuring the input trigger conditions to be mapped to the output relays via logical AND OR functions DIAGRAM The MIMO2 features two inputs and two outputs in the form of relays Wire connections can be made to the Normally Open NO or Normally Closed CO relay terminals Control and monitoring is available via Z...

Page 3: ...efault every 20 minutes SIG2 Multilevel Sensor Report Multichannel upon change of trigger or periodically Default every 20 minutes 2 2 One of the following depending on whether Endpoint 1 or Endpoint 2 SIG1 Basic Set upon change of trigger SIG2 Basic Set upon change of trigger 3 4 REL1 REL2 1 Lifeline the controller should automatically set up this association 2 One of the following depending on w...

Page 4: ...CONFIGURATION SIG1 and SIG2 Endpoints 1 and 2 The default trigger configuration for the analog inputs SIG1 and SIG2 simulates a Digital threshold around 1 6V voltage falling or 2V voltage rising That is the inputs will trigger when the input is untriggered and the level goes above approximately 2V and will reset when the level is triggered and the level goes below approximately 1 6V The trigger ra...

Page 5: ...equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to...

Page 6: ...y nature FORTREZZ LLC expressly disclaims all implied warranties including but not limited to the implied warranties of merchantability and fitness for a particular purpose FORTREZZ LLC does not warrant guarantee or make any representations regarding the use or the results of the use of the products or any accompanying materials in terms of their correctness accuracy reliability or otherwise In no...

Page 7: ... REL1 COMMAND_CLASS_SWITCH_BINARY Sets or resets REL1 COMMAND_CLASS_SENSOR_MULTILEVEL General Purpose Value type for 12 bit ADC analog SIG1 input COMMAND_CLASS_CONFIGURATION COMMAND_CLASS_SECURITY COMMAND_CLASS_MULTI_CHANNEL_V4 allows Endpoints to be commanded status ed COMMAND_CLASS_FIRMWARE_UPDATE_MD_V2 Device Type Supported Command Classes Endpoints 1 2 SIG1 SIG2 Generic Device Type GENERIC_TYP...

Page 8: ...alues over 127 to their signed numerical value 1 REL1 Configuration b7 b5 Input to Relay Mapping REL1 Basic Binary Switch commands ignored see Relay Mapping section below b4 b0 Momentary latch count resolution 100ms 0 non momentary 5 00000101b No relay mapping moment latch for 0 5s 1 128 127 0x00 0xFF 2 REL2 Configuration b7 b5 Input to Relay Mapping REL1 Basic Binary Switch commands ignored see R...

Page 9: ...Lower Threshold Low 128 Unsigned Value 128 1 128 127 0x00 0xFF 12 SIG2 Upper Threshold High 1 Unsigned Value 255 1 128 127 0x00 0xFF 13 SIG2 Upper Threshold Low Unsigned value must be greater than Lower Threshold High and less than Upper Threshold High 2 Unsigned Value 254 1 128 127 0x00 0xFF Analog Input Voltage Conversion SIG1 and SIG2 and Triggering The input signal voltage conversion to Multil...

Page 10: ...vel Sensor Command class to verify that configured trigger points correspond to the desired input voltage levels The default trigger configuration for the analog inputs SIG1 and SIG2 is a threshold around 1 85V That is the inputs will trigger when the input is untriggered and the level goes above approximately 1 85V and will reset when the level is triggered and the level goes below approximately ...

Page 11: ...48 481 7092 sales fortrezz com Made in USA 072916 The following diagrams illustrate another way of considering this triggering capability The X axis in these diagrams represent time passing from left to right The diagrams show the triggering state as the input voltage rises from zero to a certain point and then falls back to zero ...

Page 12: ... REL1 is set if SIG1 is triggered or if SIG2 is triggered cleared otherwise 2 If only bit 7 is set for the REL2 configuration then the mapping equation is REL2 state SIG1 AND SIG2 REL2 is set if SIG1 and SIG2 are both triggered cleared otherwise 3 If only bit 5 is set for the Relay 1 configuration then the mapping equation is REL1 state SIG1 REL1 is set if SIG1 is triggered cleared otherwise POWER...

Reviews: