Connecting Electric Lock
Door Lock Controlled with Internal Power
Door Lock Controlled with Volt Free Contact
1.Electronic lock, Power-on-to-unlock,
(Failsecure) should be used.
2.The door lock output is limited to 12V,
250mA.
3.The jumper should be placed on position
2 and 3 before connecting and applying
power.
4.The door lock control input (PL terminal)
is not timed.
5.The
Unlock Mode
must be set to 0 (by
default).
1.An external power supply must be used.
2.The relay contact are restricted to 24Vdc
1A.
3.The jumper must be taken off before
connecting and applying power.
4.Setup the
Unlock Mode
according to
different lock types.
•
Power-on-to-unlock type (Failse-
cure):Unlock Mode=0 (by default)
•
Power-off-to-unlock type (Fail-
safe):Unlock Mode=1
EB
*
LOCK
Jumper position on 2&3
1 2 3
L1 L2 PL S+ S-
Take off the jumper
1 2 3
L1 L2 PL S+ S-
LOCK
POWER
SUPPLY
WIRING
* FTDEV1R relay actuator is needed for 2nd lock connection.