IDDX Flame Detector Amplifier Manual
The purpose of this section is to ensure that the IDDX Flame Amplifier is installed using recommended
Forney practices.
•
The IDDX Flame Detector Amplifier must be installed in a cabinet rated to NEMA 12 ingress protection
or better to ensure it is protected from heat, dust, and moisture ingress.
•
If installed in an unventilated cabinet, forced exhaust / colling air fans may be required depending on
ambient conditions and heat loading.
•
Where ambient temperatures are expected to exceed specified limits, cabinet must be installed in a
controlled environment.
•
Ensure that the IDDX Flame Amplifier and associated cabling is located at a safe distance from high
voltage lines or other sources of electrical noise.
LOCATION
2.1
SECTION 2
EQUIPMENT INSTALLATION
NOTICE:
Ensure that the supply voltage matches the information provided in section 1.3
Technical Data prior to connecting power to the unit.
REQUIRED SITE-SERVICE
CONNECTIONS
2.2
The IDDX Flame Amplifier requires a 24VDC input from an instrument quality power supply. Forney
strongly recommends use of 24 VDC input power source with low output ripple voltage to keep power
supply induced noise to minimum.