forlong PM834 User Manual Download Page 2

上海奉义龙电子有限公司 

Shanghai Fengyilong Electronic Co,. Ltd.

                                                                     

 

___________________________________________________________________________________________ 

www.china-meters.com

     

Email

[email protected]

   

86

021-60975591/60975593 

-2-                                                                                                                                           

1      GENERAL   

 
This manual contains information about the PM834, which is a family of electronic 
electricity meters manufactured by Fengyilong.   
 
The purpose of this manual is to give the user a good overview and understanding 
of the functions and features that PM834 offers. The end goal is to help the user to 
use the meter in the most optimal and correct way and to give the proper service 
and support to maintain the highest stability and lifetime.   
 
The degree of the PM834 functions is controlled by its hardware (electronic boards, 
mechanics, etc), software (resided in a small computer inside the meter) and the 
meter type specific programming done when it is produced (stored in a non-volatile 
EEPROM memory).   
 

WARNING! 

The voltages connected to the PM834 are dangerous and can be lethal. 

Therefore it must be insured that the terminals are not touched during operation. 
When installing the PM834 all voltages must be switched off.   

 
 
2      PRODUCT DESCRIPTION 

 
This chapter contains a description of the basic functions and practical handling of 
the PM834.   
 

2.1    FAMILY OVERVIEW   

PM834 is an electronic electricity meter for 3-phase metering and is designed in 
accordance with the Fengyilong PROM standard. 

PM834  can  not  only  measure  energy  but  also  other  data,  such  as  voltage, 

current,  power,  power  factor  and  frequency.  Meter  can  display  32  items.  The 
display time of every item is 5 seconds. 
PM834 has a temperature range from –10 to +65º C (s70º C). 
PM834 has 2 ways to communicate: 
- Display at front 
- Pulse output 
The PM834 transformer connected meter has two function buttons that are used to 
set the current transformer ratio. The buttons can be sealed by mounting a 
sealable terminal cover or by mounting the PM834 in a modular enclosure. 
PM834 meter types are tested and approved according to: 
- IEC 62052-11 and 62053-21 
- Measurement instrument directive (MID), category A and B, electrical 
environmental class E2 and electrical environmental class M2     
- EN 50470-1, EN 50470-3 category A and B. 

Summary of Contents for PM834

Page 1: ...975591 60975593 1 Panel Meter User Manual PM834 Power Control Electricity Monitoring System Power Safe Programmable Management Relay Forlong Power Intelligent Power Meter Mini Power Mini Power Energy...

Page 2: ...Therefore it must be insured that the terminals are not touched during operation When installing the PM834 all voltages must be switched off 2 PRODUCT DESCRIPTION This chapter contains a description...

Page 3: ...display it is possible to view information the energy consumption and various status information The display has 7 characters of 7 segment type with a height of 6 mm and a number of other specific seg...

Page 4: ...voltage source the voltage U should be 5 27V DC and the maximum input current Imax should be 27mA DC To connect the impulse output connect 5 27V DC to connector 8 9 anode and the signal wire S to con...

Page 5: ...after 60 seconds set up the CT will be forbidden If forget to close the switch of program meter will close the program operation automatically after 60mins the disappear on LCD NOTE In the sense of s...

Page 6: ...data Power supply 65 to 275 Volts AC Universal AC DC Supply Frequency Hz 50 60Hz Frequency range 5 Temperature Operating 10 to 65 Storage 25 to 70 Humidity 75 RH Non Condensing Environment IP54 stand...

Page 7: ...____ www china meters com Email sale01 china meters com 86 021 60975591 60975593 7 voltage 5 27V DC Connection area main terminals Flexible 1 mm2 0 2 5 Solide 1 mm2 0 2 5 LED Pulse wide 80ms 20ms Puls...

Page 8: ...ified environmental conditions If degradation in the accuracy is observed the meter has probably been partly damaged for example due to lightning strike or extreme environmental conditions etc and sho...

Page 9: ...0086 21 60975593 E mail sale01 china meters com Website www china meters com CAUTION During reparation and maintenance do not touch the meters connecting clamps directly with your bare hands with meta...

Reviews: