background image

Installation Instruction:   

 

1.

 

Connect the protected equipment to “LOAD"    T1

T2 terminal. 

2.

 

Connect AC power cord to "LINE"    L1

L2 terminal. 

3.

 

The all terminals without voltage polarity restrictions. 

4.

 

To ensure the effective protection of your equipment, the ground terminal “E” must be 

grounding and grounding resistance should less 100

Ω

.   

 
 

LED Indication:   

 

1.

 

LED on: normal 

2.

 

LED off: failed   

 

 

Caution:  

 
Make sure the grounding terminal "E" connect to the lightning protection grounding. Do 
not access to the power ground wire, ground rod, and gas pipelines 

         

 

 

Specification: 

 

ITEM NO. 

SP001P-AC110 

SP001P-AC220 

Wire >150V  >300V 

Nominal 

peak 
voltage 

Wire~grounding >150V 

>300V 

Surge Current Capacity 

6000A (8x20uS) 

Surge Voltage Capacity 

6,000V    (1.2uS x 50 uS) 

Response time 

<0.1uS 

Wire 

<1mA (at150VAC) 

<1mA (at300VAC) 

Leakage 

current 

Wire~grounding <1mA 

(at150VAC) <1mA 

(at300VAC) 

Max. Load Current 

10Amp (Max) 

Temperature 

Operation: 0 to 55 C, Storage: -20 TO 85 c, Humidity: up to 95% 

Connectors Terminal 

Material Metal 

Black 

Dimensions      W x H x D mm 

87 x 67 x 27 mm   

WEIGHT                 g 

130 g  

 

 

 

2

FORESIGHT CCTV INC. | 5863 Leslie Street, Unit#713, North York, Ontario,Canada, M2H 1J8 | http://www.foresight-cctv.com | 1-888-GO2-CCTV