INDUSTRIAL FIXED GAS DETECTOR, FD-60 

FORENSICS DETECTORS

TM

 

 

 

FORENSICS DETECTORS

TM 

www.forensicsdetectors.com 

 

 
5.3. “ALARM SET” Menu 

 
Users can use this option to set the warning value and alarm mode. The detector is 
equipped with two alarm point settings. The alarm modes are LOW alarm and HIGH 
alarm values. The corresponding two sets of relays are triggered/switched. The 
instrument is in a LOW alarm state when the detected concentration is higher than 
the set LOW detected concentration value. The instrument is in a HIGH alarm state 
when the detected concentration is higher than the set concentration value. Before 
leaving the factory, the alarm value has been set. Please check the default settings to 
ensure they meet your local or preferred exposure alarm levels. 

 

The LOW alarm, corresponds to the first set of relay output (COM1 NO1, NC1) 
on the detector main board. 

 

The HIGH alarm, the second set of relay output (COM2, NO2, NC2) 
corresponds to the detector main board. 

 

The Relay (30VDC 2A/220VAC 2A) COM and NO are normally open, COM and 
NC are normally closed. 
 

5.4. Gas Zero 

Sometimes the gas sensor drifts due to electronics and sensor degradation. 
Sometimes, the sensor does not return back to its ZERO baseline. Also sometimes, the 
sensor is exposed to HIGH concentrations of toxic gas and the sensor may be 
permanently “poisoned”. Please ensure fresh air is exposed to the sensor for at least 
30 minutes, before making this determination. If the zero drift of the sensor is 
unacceptable, the user can perform a ZERO calibration operation. Pass pure nitrogen 
or clean air for at least 2 minutes through the sensor. Click on the “3. Gas Zero” menu. 
Enter into the menu items by selecting your gas then press SAVE after exposure to 
fresh air or pure nitrogen and a stable reading has been achieved. Please note, if you 
have a OXYGEN or CARBON DIOXIDE sensor, you will need to use Pure Nitrogen to 
achieve a ZERO Calibration. Other toxic gases will suffice by exposing the detector to 
fresh air. 
 

5.5. Gas Check / SPAN CALIBRATION  

Only perform calibration is you are an experience technician. Otherwise please contact 
the manufacturer for instructions. We have special calibration cap fittings to 
undertake precise calibration with (in/out) tube ports. 

 
5.6. AlarmData 

The detector can save 1000 alarm records. The interface can view the maximum 
alarm concentration in the environment recorded in the "detection interface", as well 
as the time point and alarm state of the highest concentration.  

 

Summary of Contents for FD-60

Page 1: ...TORSTM www forensicsdetectors com 1 INDUSTRIAL FIXED GAS DETECTOR Model FD 60 USER MANUAL CONFIGURATION COMPONENTS INCLUDED Serial Gas Sensor Remote Control Hex Tool 24V Wall Adapter Detector Power Cable LED Buzzer Fixture Calibration Cap QC CAL Certificate User Manual Other ...

Page 2: ...ATURES INDUSTRIAL Heavy duty fixed gas detector Comes FACTORY CALIBRATED Mount and Operate USE Remote Control up to 8 meters Analog Output 4 20mA 2 x relay alarm triggered switch 1kW to control fans pumps electrical items garage doors or additional alarms FEATURES Large LED alarm and buzzer Adjustable audio visual Alarm digital time stamp Remote Control ROBUST Explosion dust water and flame proof ...

Page 3: ...INDUSTRIAL FIXED GAS DETECTOR FD 60 FORENSICS DETECTORSTM FORENSICS DETECTORSTM www forensicsdetectors com 3 PCB Connections Remote Control ...

Page 4: ...pply DC 24V 15 Working condition Temperature 0 122F Humidity 95 RH with no condensation Storage condition Temperature 0 122F Humidity 85 RH Connection G1 2 male proof hose pipe thread size Thread size M20x1 5mm Sensor housing cap M37 x 1 5 Electrical Output 2 x relay contact output max power 1kW Communication 4 20mA only RS485 not available Weight Approx 3 pounds Dimension 200 180 90mm Warranty 1 ...

Page 5: ...m 5 F S 25s 1ppm 50ppm 100ppm CO2 0 5000ppm 5 F S 25s 1ppm 1000ppm 2000ppm H2S 0 100ppm 5 F S 30s 1ppm 10ppm 20ppm NO2 0 20ppm 5 F S 25s 0 1ppm 3ppm 10ppm NO 0 250ppm 5 F S 60s 1ppm 25ppm 50ppm SO2 0 100ppm 5 F S 30s 0 1ppm 2ppm 10pppm CL2 0 20ppm 5 F S 30s 0 1ppm 1ppm 10ppm NH3 0 100ppm 5 F S 50s 1ppm 25ppm 50ppm H2 0 1000ppm 5 F S 60s 1ppm 50ppm 10ppm HCN 0 50ppm 5 F S 200s 0 1ppm 10ppm 20ppm HC...

Page 6: ...e detector has been FACTORY calibrated Hence it is NOT necessary to perform any CALIBRATION however do ensure ALARMS are set to the users satisfaction and local exposure limit requirements as necessary per your safety officer advice or consult with local state or federal authorities The detector can be turned off by directly disconnecting the power supply We recommend BUMP testing to confirm opera...

Page 7: ...hannel Set Manufacturer only access 3 Host Set 4mA Manufacturer only access 4 Host Set 20mA Manufacturer only access 5 Set Max Manufacturer only access 6 Save Factory Manufacturer only access 7 Reset Factory Manufacturer only access 8 System Info Summarized alarms and Software Version 9 Language English or Chinese MAIN MENU 1 Back 2 Setting 3 AlarmSet 4 Gas Zero 5 Gas Check 6 AlarmData 7 Time Set ...

Page 8: ...degradation Sometimes the sensor does not return back to its ZERO baseline Also sometimes the sensor is exposed to HIGH concentrations of toxic gas and the sensor may be permanently poisoned Please ensure fresh air is exposed to the sensor for at least 30 minutes before making this determination If the zero drift of the sensor is unacceptable the user can perform a ZERO calibration operation Pass ...

Page 9: ...r example in very cold or very hot environment 0 122F Do not install within 5 ft of heating or cooking appliances Do not install near vents flues chimneys or air ventilation openings Do not install near ceiling fans doors windows or areas directly exposed to the weather so external air water or rain reaches the detector Do not install in dead air spaces such as peaks of vaulted ceilings or gabled ...

Page 10: ...TED VAPORS HARSH CHEMICALS OR EXTREMELY HIGH CONCENTRATION LEVELS AS IT MAY POISON THE SENSOR SEE APPENDIX FOR RANGES Ø FOLLOW INSTRUCTIONS AS THE DETECTOR IS VERY SENSITIVE Ø Connect the cable according to the Ex request The end of the cable need to be treated properly and should be connected to Ex junction box or equipment When the detector doesn t need to work with the controller the block is n...

Page 11: ...hird parties We shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty Except to the extent prohibited by applicable law any implied warranty of merchantability or fitness for a particular purpose is limited in duration for 1 year THIS PRODUCT CANNOT BE REPAIRED IF THE UNIT IS TAMPERED WITH IT WILL INVALIDATE THE GUARANTEE IF THE UNI...