appliance main burners are operating.
P. Check ignition system safety shut-off device.
After control has finished sparking, remove ignitor/
flame sense wire from control. Burners will shut
down.
Q. Test LWCO functionality
Press "TEST"/SETTINGS button on Hydrostat
3200. Boiler should shut down.
• Set thermostat to call for heat and push
“TEST”/SETTINGS button on Hydrostat 3200
to simulate low water condition.
• Red “LOW WATER” LED will illuminate and
burner will shut down.
• Release “TEST”/SETTINGS button and burner
will light off.
R. Check high limit control. Set thermostat to
higher than normal setpoint. Allow boiler to run
until high limit is achieved. (190oF default) Burners
will shut down.
S. Check thermostat operation. Raise and lower
temperature setting to start and stop boiler
operation. Adjust thermostat to normal setting.
T. Review User's Information Manual and system
operation with owner or operator.