FR-DCMG DC System Monitor User Manual Fonrich New Energy Technology Co., Ltd.
0x00B8
Channel 23 arc fault alarm
counter
Unsigned
short
Record arc fault occurs in channel
R
0x00B9
Channel 24 arc fault alarm
counter
Unsigned
short
Record arc fault occurs in channel
R
0x00BA
Bus-bar arc fault alarm
counter
Unsigned
short
Record arc fault occurs in bus-bar
R
0xXX** type registers is used to store the data that received from the wireless node. XX means the address
of the wireless node which can not bigger than the supported wireless node number, FWB NODE and
NODBUS mode do not support these registers.
0xXX00
Voltage of the bus wire of
the wireless node
Short
Unit V
R
0xXX01
0xXX02
state of the input switch of
the wireless node
Unsigned
short
Bit0 indicate the first input switch,
bit1indicate the second input
switch, so on and so forth.
0 means break
1 means close
R
0xXX03
Arc fault alarm flag
Unsigned
short
Has arc fault in this node.
R
0xXX04
Temperature of the wireless
node
Short
The detected value of temperature
sensor ,unit 0.1ºC
R
0xXX05
The quantity of the
channels of the wireless
node
Unsigned
short
The detected number of current
channels
R
0xXX06
Distance to gateway of the
wireless node
Unsigned
short
When the device is used as wireless
node, this indicate the distance to
gateway, 0 means offline. Other
mode this equal to 0
R
0xXX07
Leakage current value
Short
The detected value of leakage
current sensor ,unit 0.1mA
R
0xXX08
Current of channel 1 of the
wireless node
Short
Unit mA,symbol means direction
R
0xXX09
Current of channel 2 of the
wireless node
Short
Unit mA,symbol means direction
R
...
...
31