34
Type C13
Boiler intended for connection to horizontal outlet
and intake ducts connected to the outside by means
of coaxial or split ducts.
The distance between the air intake duct and the flue
gas outlet duct is to be a minimum of 50 mm, and
both terminals are to be positioned within a squared
area having 500 mm sides.
The boiler is to be equipped by a fan mounted before
the combustion chamber/heat exchanger.
Type C33
Boiler intended for connection to vertical outlet and
intake ducts connected to the outside by means of
coaxial or split ducts.
The distance between air intake duct and flue gas
flue duct is to be a minimum of 50 mm, and both
ends are to be positioned within a squared area hav-
ing 500 mm sides.
The boiler is to be equipped by a fan mounted before
the combustion chamber/heat exchanger.
Type C43
Boiler intended for connection to collective chimney
pipe system that includes two ducts, air intake and
flue gas exhaustion.
These ducts may be coaxial or split. The flue gas
chimney system must comply with current standards.
The boiler is to be equipped by a fan mounted before
the combustion chamber/heat exchanger.
Type C53
Boiler with separate pipes for air intake and flue gas.
Air and flue gas may be have different exhaustion
pressure.
Air and flue gas terminals may not face each other
from opposite walls. The boiler is to be equipped by
a fan mounted before the combustion chamber/heat
exchanger.
Before the combustion chamber/heat exchanger.
Type C83
Boiler intended to be connected to combustion air terminal and to a single flue gas terminal or col-
lective chimney.
Flue gas chimney must comply with current standards.
The boiler is to be equipped by a fan mounted before the combustion chamber/heat exchanger.