AST 14 C 258/00
7.4 Ø 60 SPLIT VENT DUCT
Pipe maximum length
Type of installation B23 - B53*
TYPE OF
INSTALLATION
PIPING MATERIAL
KRB 12
KC-KRB 24
KC-KRB 28
Air
intake
Vent
Flue gas
L max
[m]
L max
[m]
L max
[m]
B23; B53; C63
----
polypropylene
39 23 23
* The minimum length of discharge line must be one meter
Ø 60 duct load loss table
Part
Vent
[m]
Intake [m]
12 kW
24 kW
28 kW
12 kW
24 kW
28 kW
Wall vent terminal
4
4.5
-
1 m extension
1 1
0.5 m extension
0.5 0.5
90° elbow
1 1
45° elbow
0.5 0.5
60 mm tee with condensate discharge
0.5 -
60 mm tee
0.5 0,5
1