84
Instructions for the installer
3.18.3 Edit parameter P0-TSP0
1. Press
and
ON
at the same time for
three seconds.
2. Scroll through the parameters by pressing
CH +/-
buttons. As soon as you reach the
one to be modiied, press
OK
.
3. The wrench symbol turns on and indicates
you can edit the parameter value.
4. The parameter value can be edited using
CH +/-
buttons.
5. To conirm modiication press
Ok
.
6. To quit editing mode without changing the parameter press
.
Boiler settings
Parameter P0-TSP0 value
12 kW Natural gas
0
12 kW Propane
5
24 kW Methane
1
24 kW Propane
3
28 kW Methane
2
28 kW Propane
4
32 kW Methane
6
32 kW Propane
7
Tab. 24 Table
7. Adjust the gas valve (see
Gas valve setting
on page
84
).
3.18.4 Gas valve setting
Maximum heating output adjustment
•
Make sure that the ambient thermostat (optional), if itted, is set to
ON
.
•
Select the "heating" mode on the control panel pressing key
n times until symbol
is displayed.
•
Start the ‘lue cleaning’ function by keeping
key pressed until symbol
stops lashing. Boiler switches to max. output operation.
•
If a gas switching has been made, access the programming page and set the parameter
P0
based on the power and on the gas, as speciied
in Tab. 16 Limits to be set for TSP parameters and default values in relation to boiler type (TSP0).
•
Set lue gas CO2 content by turning the ratio adjuster
B
(see Fig. 38 Adjusting CO2 value) and ensure that reading falls within the limits of
Tab. 25 Flue CO2 content. Let boiler lue cleaning function on and continue with the next point ”Minimum heating output adjustment" .
Minimum heating output adjustment
•
Set boiler min. output operation by keeping
CH -
button pressed until the value corresponding to fan min. speed for the output and boiler
gas is displayed (refer to Tab. 16 Limits to be set for TSP parameters and default values in relation to boiler type (TSP0).
•
Boiler switches to min. output operation.
•
Set lue gas CO2 content by turning the ofset control
C
(see Fig. 38 Adjusting CO2 value) and ensure that reading falls within the limits of
Tab. 25 Flue CO2 content.
•
Keep key
pressed to end the lue cleaning function.