- Remove the front part of combustion chamber as shown in fig. 41;
fig. 41
- Remove the main burner;
- Remove nozzles from main burner replacing them by new gas type correct diameter ones.
WARNING! the copper gaskets must be installed;
- Reinstall the main burner;
- Modify parameter
P00
value according to boiler power, following table 18.
Default
Parameter
P00
24 kW LPG
0
24 kW Natural gas
1
28 kW LPG
2
28 kW Natural gas
3
tab. 18 - P00 parameter setting
1-
To modify parameter
P00
it is necessary
to press “reset” and
“operating mode” keys at
the same time, for three
seconds.
2-
Parameters can be
scrolled by pressing “CH
+/- “ buttons. As soon as
you reach the one to be
modified, press “ok”. The
wrench symbol turns on
and indicates you can
edit the parameter value.
3 -
The parameter value
can be edited using
“CH + and -” buttons.
If you quit using the
“reset” button, the
parameter will not save
changes and remain set
to previous value. To
confirm modification
you must press “ok”.
- Adjust the gas valve (see next paragraph, 3.7.3.).