HCD1010A/W, HCD1010A/W, HCD1410A/W, HCD1410A/W
5
Specifications
Electrical
Separate circuit and equipment ground required.
Evaporator unit
Standard electrical: 115/60/1
Maximum fuse: 15A
Amperage: 5A
Condensing unit
1010 Single-Phase
1010 3-Phase
1410 Single-Phase
1410 3-Phase
Electrical
208-230V, 60Hz
208-230V, 60Hz
208-230V, 60Hz
208-230V, 60Hz
Max Circuit HVACR breaker size
15A
15A
30A
25A
Min Circuit Ampacity
10.7A
9 .9A
19.3A
14.2A
Evaporator plumbing
§
3/8" OD push-in water inlet (connection inside machine) - 3/8" OD tubing required
§
3/4" MPT
§
3/4" drain line must slope a minimum of 1/4" per foot (6 mm per 30.4 cm run).
§
Drain to be hard piped and insulated.
§
Water shut-off recommended within 10 feet (3 m).
§
Follett recommends installation of Follett water filter system (part# 00130286) in ice machine inlet water line.
Ambient
Evaporator unit
Air temperature
100 F/38 C max.
50 F/10 C min.
Water temperature
90 F/32 C max.
45 F/7 C min.
Water pressure
70 psi max. (483 kPa)
10 psi min. (69 kPa)
Condenser unit
Air temperature
120 F/49 C max.
–20F/–29C min.
Refrigeration
§
3/8" liquid line
§
5/8" suction line
Note:
Rack system installations require a capacity of 10,000 BTU/hr for 1010 machines and 13,000 BTU/hr for
1410 machinesat 0 F (–18 C) evaporator temperature. Evaporator pressure regulator (not supplied) is
required.
Weight
Evaporator unit: 125 lbs (57 kg)
Condensing unit: 225 lbs (102 kg)