FOLKNOLL DISABLED REFUGE EVC Manual Download Page 24

 

Folknoll Group Ltd.

 

OLD NORTH RD, ROYSTON HERTS, SG8 5TD, UK 

TEL: +44 (0) 1763 234567 

EMAIL: 

[email protected]

 

WEB: 

WWW.FOLKNOLL.CO.UK

 

 

E+EO (C) FOLKNOLL GROUP LTD 2010-2018 

 

 

Summary of Contents for DISABLED REFUGE EVC

Page 1: ...Folknoll Group Ltd File DR 7700 000 SM7 V100 Refuge EVC Manual 3 Zone Docx E EO c 2018 Folknoll Group Ltd DISABLED REFUGE EVC 3 ZONE REFUGE EVC SYSTEM MANUAL...

Page 2: ...1 1 System Controller Addressing 7 4 1 2 Fault Monitoring 7 4 1 3 Master Station Controls Enable 7 4 1 4 Initial Power Up 8 4 1 5 Outstation Configuration 8 4 1 6 Volume and Microphone Gain Adjustmen...

Page 3: ...eries 16 8 2 VISUAL INSPECTION 16 8 2 1 Outstations 16 8 2 2 Master Station 16 8 2 3 Controller PSU Cables 17 8 3 FUNCTIONAL TESTING 17 8 3 1 User Call Check 17 8 3 2 Operator Call Check 17 8 3 3 All...

Page 4: ...ny of our range of refuge outstations can be used in conjunction with our 3 zone refuge systems offering a range of vandal resistance IP rating and DDA compatibility to suit your site 1 1 3 3 Zone Mas...

Page 5: ...of our products and systems are designed for toughness reliability easy installation simple configuration straightforward operation and low maintenance As original manufacturer all of our product ran...

Page 6: ...ETUF CABLES In a standard 3 Zone system there is a single controller with battery backed PSU which provides control and power to the entire system All devices are star wired to the controller the cont...

Page 7: ...8 Folknoll Group Ltd PAGE 4 3 3 ZONE REFUGE EVC CONNECTIONS All connection is via terminal block located within the equipment Folknoll s design has allowed sufficient room for glands for larger fire r...

Page 8: ...V1 00 File DR 7700 000 SM7 V100 Refuge EVC Manual 3 Zone Docx E EO c 2018 Folknoll Group Ltd PAGE 5 3 2 3 ZONE OUTSTATION WITH LOOP Figure 3 Typical 3 Zone Outstation with Induction Loop Connection US...

Page 9: ...STEM MANUAL V1 00 File DR 7700 000 SM7 V100 Refuge EVC Manual 3 Zone Docx E EO c 2018 Folknoll Group Ltd PAGE 6 3 3 3 ZONE MASTER STATION CONNECTION Figure 4 Typical 3 Zone Master Connection USUALLY 4...

Page 10: ...fuge EVC system is installed and ready to power up fault monitoring should be enabled by setting both PCB dip switches to on The monitoring circuit will report power fail until power is applied press...

Page 11: ...power LED will illuminate and it will report a fault until configuration has been completed see section 4 1 5 Outstation Configuration below 4 1 5 Outstation Configuration The system is configured by...

Page 12: ...ser and the persons operating the system from the master station as the operator THIS SYSTEM SHOULD BE OPERATED IN ACCORDANCE TO THE RELEVANT STANDARDS AND REGULATIONS Figure 6 Master Station Panel 5...

Page 13: ...stem To talk to a user the operator must press and hold the TALK button Whilst the TALK button is held the operator will not be able to hear the user 5 2 3 To Cancel an Incoming Call from an Outstatio...

Page 14: ...ged has arrived please standby 5 4 1 To Make an All Call The operator should ensure that no outstation calls are in progress i e none of the outstation buttons are illuminated If necessary any current...

Page 15: ...E g EVC operator how can I help The user should wait for the operator to finish talking before answering If the user interrupts the operator the operator will not be able to hear the user 6 1 2 To Can...

Page 16: ...e Docx E EO c 2018 Folknoll Group Ltd PAGE 13 6 3 ALL CALLS AND ANNOUNCEMENTS The operator may choose to make an All Call or announcement to all outstations E g This an announcement for all refuge use...

Page 17: ...urn and report any errors found DURING TESTING OUTSTATIONS WILL GENERATE AUDIO TONES TESTING SHOULD BE TIMED TO MINIMISE INCONVENIENCE 7 3 AUDIO PATH TEST TRIGGERED EXTERNALLY A full audio path test c...

Page 18: ...E STANDBY BATTERIES WILL DISCHARGE AND THE SYSTEM WILL NOT OPERATE 7 4 2 Master Station Disabled The master station will not respond to button press To rectify the fault override the remote controls e...

Page 19: ...ry 2 years 8 2 VISUAL INSPECTION Disabled Refuge EVC systems are usually located in public areas and depending on location can be open to abuse The frequency of visual inspections should be determined...

Page 20: ...the call The outstation user can be clearly heard by the master station operator The master station operator can be clearly heard by the outstation user The call can be cancelled by the master station...

Page 21: ...e reaches 19V to prevent full discharge THIS TEST SHOULD NOT BE CARRIED OUT ON A LIVE SYSTEM BECAUSE THE SYSTEM WILL FAIL AT SOME POINT WHEN THE POWER IS RESTORED THE STANDBY TIME WILL BE REDUCED EITH...

Page 22: ...DISABLED REFUGE EVC PAGE 19 3 ZONE REFUGE EVC SYSTEM MANUAL V1 00 File DR 7700 000 SM7 V100 Refuge EVC Manual 3 Zone Docx E EO c 2018 Folknoll Group Ltd PAGE 19 9 APPENDIX A FIRETUF CABLES...

Page 23: ...DISABLED REFUGE EVC PAGE 20 3 ZONE REFUGE EVC SYSTEM MANUAL V1 00 File DR 7700 000 SM7 V100 Refuge EVC Manual 3 Zone Docx E EO c 2018 Folknoll Group Ltd PAGE 20...

Page 24: ...Folknoll Group Ltd OLD NORTH RD ROYSTON HERTS SG8 5TD UK TEL 44 0 1763 234567 EMAIL SALES FOLKNOLL CO UK WEB WWW FOLKNOLL CO UK E EO C FOLKNOLL GROUP LTD 2010 2018...

Reviews: