DISABLED REFUGE EVC
PAGE 15
3-ZONE REFUGE EVC SYSTEM MANUAL V1.00
File:DR 7700-000 SM7 V100 Refuge EVC Manual 3-Zone.Docx E+EO (c) 2018 Folknoll Group Ltd
PAGE 15
7.4.1
Mains Power Fault
•
The master station will continuously emit 2 short bleeps and one long bleep
•
The master station fault LED will continuously give 2 short flashes and one long flash
The system will continue to operate from its standby power supply.
If fully charged the system will operate for at least 24 hours in standby and at least 30 minutes of
alarm active.
The sounder can be silenced by pressing the
MUTE
button.
The mains supply should be restored as soon as possible.
IF THE POWER IS NOT RESTORED THE STANDBY BATTERIES WILL DISCHARGE AND THE SYSTEM
WILL NOT OPERATE
7.4.2
Master Station Disabled
•
The master station will not respond to button press
To rectify the fault, override the remote controls enable, if fitted, or check the enable link please refer
to section 4.1.3 Master Station Controls Enable.
7.4.3
Audio Path Fault
Audio path tests are performed if the
TEST
button is pressed or when triggered by the external timer
or management system. If an outstation fails an audio path test:
•
The master station will continuously emit 2 short bleeps and one long bleep
•
The master station fault LED will continuously give 2 short flashes and one long flash
•
The sounder can be silenced by pressing the
MUTE
button
The fault should be reported / repaired according to the local fault reporting procedure.
THE OUTSTATION INDICATED MAY NOT BE OPERATIONAL UNTIL THE FAULT IS RECTIFIED