C. TERMINAL LOCATIONS WALL MOUNTING
Dimension Terminal Locations
Distance (mm)
A*
Directly below an opening, air brick, opening window, etc.
600
B
Above an opening, air brick, opening window, etc.
300
C
Adjacent to an opening, air brick, opening window, etc.
400
D
Below gutters, soil pipes or drain pipes
300
E
Below eaves
300
F
Below balconies of car port roof
600
G
From a vertical drain pipe or soil pipe
300
H
From a internal or external corner
600
I
Above ground roof or balcony level
300
J
From a surface facing the terminal
600
K
From a terminal facing the terminal
600
L
From an opening in the car port (e.g. door, window into the dwelling).
1200
M
Vertically from a terminal on the same wall
1500
N
Horizontally from a terminal on the same wall
300
P
From a vertical structure on the roof
600
Q
Above intersection with roof
150
* I addition, the terminal should not be nearer than 300mm to an opening in the building fabric formed for the purpose of accomodating a built in element
such as a window frame.
Installer section