OTHER FEATURES 

 
 
 

Modbus  Communication: 

Modbus  RTU  ve  Modbus  TCP  ile  haberleşmeyi 

desteklemektedir. 5 connections can be provided simultaneously with Modbus TCP. Up to 
32 devices can be connected with the Modbus RTU from each serial port. 

 

 

Speed  PLC  BUS:

  With  the  Speed  PLC  BUS  communication  protocol  which 

developed  by  Fultek  Control  Systems,  intelligent  read  and  the  ability  to  write  different 
data fields features  provides  faster  communication.  You  can  find  detailed information in 
the help section of the Speed PLC program. 

 

MAC Address: 

The MAC address of the integrated PLC module is located on the 

product label. If you wish, you can change the MAC address in the DB0 data block with 

the  Speed  PLC  program.  When  changing  the  MAC  address,  check  that  the  same  MAC 
address is not on the network. Do not forget that communication problems with the PLC 
may occur in case of conflicting MAC addresses. 

 

 

 
 
 
 
 

Ethernet Connection:

 

If  you  wish, you 

can  connect  the  integrated  PLC  module 
on  your  local  network  or  connect  it 

directly  on  your  computer  without  cross 
cable.  To  make  a  direct  connection  to 
your computer, you must set  settings of 

your  network  adapter,  as  shown  in  the 
figure  and  then  connect  the  Ethernet 

cable. 

 
Factory Settings: 

Off the power of integrated PLC module. Supply the integrated 

PLC  module  while  pressing  and  holding  the  PLC  Run/Stop  button.  Release  the  button 

when the Run LED is turned on, the PLC will return to the factory settings. COM0 Serial 
port at factory settings: 115200 bps, none parity, 1 stop bit, 8 data bit.  
IP address factory setting: 192.168.0.10. Modbus PLC address factory setting: 0. 

 
 

RTC:

 Real Time Clock life is 30 days, during this time if the PLC is not energized, 

System Fault LED lights on. You can remove this warning  when you update the system 

time in Speed PLC DB0. 
 
 

 

Summary of Contents for HMI Basic

Page 1: ...FOCUS HMI PLC USER MANUAL...

Page 2: ...A7 4 Core 1 2 GHz ARM Cortex A7 4 Core 1 2 GHz ARM Cortex A7 4 Core 1 3 GHz Ram 7 10 1 512 MB DDR3 1 GB DDR3 512 MB DDR3 1 GB DDR3 1 GB DDR3 Graphics Processor GPU Mali400MP2 600 MHz Mali400MP2 600 MH...

Page 3: ...he Focus HMI with integrated Fulmatic 7 PLC The integrated PLC has a maximum of 40 IO It can be expanded up to 16384 IO capacity with Fulmatic 7 Remote IO modules The integrated PLC is programmed with...

Page 4: ...alog Input Output 2 x 0 10 V 0 20 mA selectable 12 bit Analog Input and 4 x 16 bit selectable Analog Input 1 x 0 10 V and 1 x 0 20 mA Analog Output 2x Serial Port It is selected according to the model...

Page 5: ...ection diagram Sections of the cables that connect to terminals should be taken into consideration The cables to be connected must be used by stripping them to the point where they can enter into the...

Page 6: ...ction Terminal 1 24 V Terminal Supply 24 V Terminal Supply 2 0 V Terminal Supply 0 V Terminal Supply 3 COM0 A Endpoint COM0 A Endpoint 4 COM0 B Endpoint COM0 B Endpoint 5 0 V Terminal Supply 0 V Termi...

Page 7: ...ion Terminal 1 24 V Terminal Supply 2 I 0 0 Input 3 I 0 1 Input 4 I 0 2 Input 5 I 0 3 Input 6 I 0 4 Input 7 I 0 5 Input 8 I 0 6 Input 9 I 0 7 Input 10 0 V Terminal Supply 10 DQ0 Connection Terminal 1...

Page 8: ...D 10 13 PLC LED Block 1 Power on LED 2 Run LED 3 Fault LED 4 COM0 A1 TX1 LED 5 COM0 B1 RX1 LED 6 COM1 A2 TX2 LED 7 COM1 B2 RX2 LED 8 9 10 Stop LED No Connection Point Description for model PP XXXXXX X...

Page 9: ...etected by the PLC When defined as normal digital input it is read once in each PLC cycle Use of Digital Inputs Digital inputs may be used as digital inputs or It can also be used as Rising Edge Count...

Page 10: ...ed on the falling edge of the signal applied to the input The value in the counter becomes 1 when the signal applied to the input drops to the logic 0 level after logic 1 and the value in the counter...

Page 11: ...be connected to the next input and Z pin should be connected to the next input Frequency 1000ms It is the input type which counts the pulses applied to the input within 1000 ms The count is repeated e...

Page 12: ...e and the falling edge of the signal applied to the input Fast Counter When the inputs are used as a fast counter it reads 1 channel at 200 kHz 3 channels at 150 kHz or 8 channels at 100 kHz Analog In...

Page 13: ...Tic Ltd Sti Address Buyuksehir Mah Cumhuriyet Cad Ekinoks E2 Blok K 2 D 8 Beylikduzu ISTANBUL Phone 90 212 871 0128 Email info fultek com tr Web site www fultek com tr 2 Wire Transmitter Connection 3...

Page 14: ...Address Buyuksehir Mah Cumhuriyet Cad Ekinoks E2 Blok K 2 D 8 Beylikduzu ISTANBUL Phone 90 212 871 0128 Email info fultek com tr Web site www fultek com tr Use of Analog Inputs 2 Wire PT100 Connectio...

Page 15: ...71 0128 Email info fultek com tr Web site www fultek com tr Single Channel Loadcell Two Channel Loadcell Use of Analog Inputs Single Channel Loadcell Connection Excitation V1 Signal AI4 Signal AI5 Exc...

Page 16: ...Digital Outputs PWM Output Hardware PWM Pulse Width Modulation is a function that allows to control the supplied electricity by changing the logic 1 residence times of generated square wave a certain...

Page 17: ...program apart from hardware PWM software PWM is also available Hardware PWM described in this section For software PWM you can refer to the help pages of the Speed PLC program PTO Outputs PTO pulse t...

Page 18: ...90 212 871 0128 Email info fultek com tr Web site www fultek com tr Analog Outputs There are two outputs 0 10V from the AQ0 analog output channel and 0 20mA from the AQ1 analog output channel The ana...

Page 19: ...k with the Speed PLC program When changing the MAC address check that the same MAC address is not on the network Do not forget that communication problems with the PLC may occur in case of conflicting...

Reviews: