background image

2.0 APPLIANCE DATA

Model

Country of

Destination Cat Gas Type

Operating Pressure

(±2.0 mbar)

Max Energy Input (kW) Min Energy Input (kW)

G20 G25 G30 G31

Gross

Net

Gross

Net

P23 Natural Gas Models

GB - IE

I2H Natural 20

-

-

-

2.0

1.8

1.0

0.9

P23 LPG models

GB - IE

I3P Propane

-

-

-

37

1.7

1.55

1.0

0.92

L23 Natural Gas Models

GB - IE

I2H Natural 20

-

-

-

2.0

1.8

1.3

1.15

L23 LPG models

GB - IE

I3P Propane

-

-

-

37

1.7

1.55

1.3

1.2

GB IE

©

2016 Focal Point Fires plc.

3.0 INSTALLATION REQUIREMENTS

If the appliance is to be sited near a disused or unserviceable fireplace served by a natural draught flue then the old flue must be

sealed off. It will be necessary to ventilate the old flue to prevent condensation and dampness forming, however any air vent used to

ventilate the old flue must not be sited within 500mm of this appliance. If the flue can be ventilated to the outside of the building

then this is usually the best solution. If in doubt then advice should be sought from a local building control officer.  The appliance is

designed to be wall mounted. If the appliance is to be mounted on a newly fabricated area of wall that also serves the purpose of

sealing off the old flue then it is very important that there are no holes, gaps or otherwise in this wall that will allow draughts from

the old flue to enter the room, especially directly behind the appliance. Such draughts could affect the performance of the ODS sys-

tem and result in nuisance cutting out, for example. If the gas supply pipe is to enter the appliance from the rear, i.e. emerge from

the wall behind the appliance, then any hole in the wall from which the pipe emerges must be tightly sealed. Propane/LPG models

must not be installed in cellars, basements or any room which is completely below ground level.

All Models : The room size MUST be a minimum of 23m

3

(e.g. 10’1” x 10’1” x 8’) to allow adequate circulation of air and

ensure the correct operation of the fire. This volume may include adjacent spaces but these spaces must not be separated by a

door. To calculate a room size in cubic metres (m

3

) divide the room volume in cubic feet (ft

3

) by 35.3. 

This appliance may be installed in any room in the home except bathrooms. In accor-

dance with BS5871 part 4, installation in bedrooms is permitted. If the appliance is to

be installed in a bedroom then an electronic carbon monoxide detector complying with

the current edition of BSEN 50291 must be installed in the same room as the appli-

ance. For maximum safety it is recommended that such device is continuously (mains)

powered and arranged in such a way that the gas supply to the appliance is isolated in

the event of an alarm. The selection and installation of such device shall be in accor-

dance with the current edition of BSEN 50292, and the user must be briefed regarding the use and maintenance of such a device.

The appliance is designed to be versatile, and as such will operate correctly when exposed to normal gentle draughts experienced with-

in the home. It is not recommended, however that the appliance be installed in areas where it is likely to be directly exposed to persist-

ent strong draughts, that may be generated by outside doors, windows, air vents, air conditioning units, extractor fans, ceiling fans etc. See

section 4.1 for more information on ventilation.

Clearances to non-combustible materials

Non combustible surfaces are defined as brick, metal, marble, concrete etc. and also a number of man-made materials impervious

to flame. If in doubt refer to the material manufacturer for further information before proceeding with installation.

Clearances to the sides of the appliance are 100mm (4”). Clearance to the front of the appliance is 500mm (20”). 

The back of the appliance may be installed directly onto a non-combustible wall, providing the area behind the appliance is flat

and does not interfere with the various vent holes in the back panel of the appliance. A non combustible shelf of any depth may

be positioned above the appliance provided it is no closer than 400mm (16”) from the top of the appliance glass panel and the

wall above the appliance is non combustible. The appliance must not be positioned vertically within 60mm (2.4”) of a solid floor

(i.e. wood or stone) or hearth.  This dimension is measured vertically to the bottom of the appliance firebox.

Clearances to combustible materials

Combustible materials are defined as wood, fabrics, or other materials likely to combust if exposed to flame. Generally, any mate-

rial, which is likely to discolour, melt or misshape when exposed to moderate heat, should be considered as a combustible mate-

rial or surface. Clearance to the sides of the appliance are 100mm (4”) but curtains, drapes and other fabrics are not permitted

within a distance of 500mm (20”) of the appliance sides. No such materials are permitted directly above the appliance regardless

of distance. 

3.1 ROOM SIZING

4.0 SITE REQUIREMENTS

This appliance is designed to be

wall-hung. Do not recess any part

of the appliance into the wall.

WARNING

3

Specifications

NG Models

LPG Models

Main burner Flow Restrictor

Stereo 1.00

Stereo 0.65

Oxypilot 

SIT 9082/ Copreci 21100 2F/ 296

SIT 9286/Seagas P5-19

Gas Control

Copreci 21400 

Copreci 21400

Gas Inlet 

8mm restrictor elbow

8mm restrictor elbow

Ignition

Double Piezo Spark

Double Piezo Spark

Spark Gap

3.5 - 4.5mm

3.5 - 4.5mm

Please see Data Badge affixed to appliance for current data.

This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.

Summary of Contents for L23 CHESHIRE

Page 1: ...ages and layout of this booklet is owned by Focal Point Fires plc You are not permitted to copy or adapt any of the con tent without the prior written permission of Focal Point Fires plc Revision F 03...

Page 2: ...should not be used in a room without some form of background heating present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the ro...

Page 3: ...ection and installation of such device shall be in accor dance with the current edition of BSEN 50292 and the user must be briefed regarding the use and maintenance of such a device The appliance is d...

Page 4: ...any vapour control bar rier is not damaged and that any structural members of the house frame are not damaged refer to section 7 0 The appliance must not be positioned vertically within 100 mm 4 of a...

Page 5: ...eaf of a conven tional cavity brick wall or a solid wall then the wall plugs and fixing screws provided may be used Depending on the condition of the wall it may be necessary to use additional fixings...

Page 6: ...e knob depressed in the nine o clock position for approximately ten seconds Now release the knob and the pilot should stay alight If the pilot is extinguished during use wait three min utes before rep...

Page 7: ...e glass facia panel is supported by four M6 screws which protrude from the front of the outer casing Ensure each screw is unscrewed approximately one turn from the fully screwed in posi tion in order...

Page 8: ...head Check the aeration holes are free from lint or dirt The pilot assembly can be removed if required by disconnecting the electrode HT lead gas pipe and unscrewing the mounting screws and lifting aw...

Page 9: ...O concentration as displayed by the analyser also noting the units in which the values are expressed Most analysers display carbon dioxide CO2 concentrations in percentage terms and carbon monoxide co...

Page 10: ...there is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thorou...

Page 11: ...cess of 11 000 hours 10 years of normal use After this time the catalyst should be replaced Should any home improvements be carried out to the property after the fire is installed such as installation...

Page 12: ...ntly fixed in position or can be moveable and can incorporate open fires including combination grates or closed fires including room heaters and stoves See figures 2 3 for fireguard examples The fireg...

Page 13: ...low the appliance to be used until the appliance and installation is passed as safe If the pilot continues to be extinguished you must call your installer to check the operation of the complete applia...

Page 14: ...ems such as any ceramics including coals pebbles the matrix front strips side cheeks rear panels and tapered rear panels are not covered by the 3 year guarantee For all Electric fires purchased the 3...

Reviews: