Focal Point DALVIK Installation And User Instructions Manual Download Page 3

2.0 APPLIANCE DATA

3

Destination Country

Gas Type

Cat

Inlet/Operating 

Pressure (±2.0 mbar) Max Energy Input (kW) Min Energy Input (kW)

G20 G25 G30 G31

Gross

Net

Gross

Net

GB - IE

Natural

I2H

20

-

-

-

3.1

2.8

1.5

1.35

Propane

I3P I3+

-

-

-

37

3.1

2.8

1.5

1.35

GB IE

Please see Data Badge affixed to appliance for current data.

This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.

If the appliance is to be sited near a disused or unserviceable fireplace served by a natural draught flue then the old flue must be sealed

off. It will be necessary to ventilate the old flue to prevent condensation and dampness forming, however any air vent used to ventilate

the old flue must not be sited within 1000mm of this appliance. If the flue can be ventilated to the outside of the building then this is

usually the best solution. If in doubt then advice should be sought from a local building control officer.  The appliance is designed to be

floor mounted. If the appliance is to be mounted in front of a newly fabricated area of wall that also serves the purpose of sealing off

the old flue then it is very important that there are no holes, gaps or otherwise in this wall that will allow draughts from the old flue to

enter the room, especially directly behind the appliance. Such draughts could affect the performance of the ODS system and result in

nuisance cutting out, for example. If the gas supply pipe is to enter the appliance from the rear, i.e. emerge from the wall behind the appli-

ance, then any hole in the wall from which the pipe emerges must be tightly sealed. Propane/LPG models must not be installed in cellars,

basements or any room which is completely below ground level.

The room size MUST be a minimum of 35m

3

(e.g. 3.8m x 3.8m x 2.425m or 12'5" x 12'5" x 8'). 

This is to allow adequate circulation of air and ensure the correct operation of the fire. This volume may include adjacent spaces but

these spaces must not be separated by a door.  Note : To calculate a room size in cubic metres (m

3

) divide the room volume in cubic

feet (ft

3

) by 35.3. 

This appliance may be installed in any room in the home except bathrooms. In accordance with BS5871 part 4, installation in bedrooms

is permitted. If the appliance is to be installed in a bedroom then an electronic carbon monoxide detector complying with the current

edition of BSEN 50291 must be installed in the same room as the appliance. For maximum safety it is recommended that such device is

continuously (mains) powered and arranged in such a way that the gas supply

to the appliance is isolated in the event of an alarm. The selection and instal-

lation of such device shall be in accordance with the current edition of BSEN

50292, and the user must be briefed regarding the use and maintenance of

such a device.  

The appliance is designed to be versatile, and as such will operate correctly

when exposed to normal gentle draughts experienced within the home. It is

not recommended, however that the appliance be installed in areas where it

is likely to be directly exposed to persistent strong draughts, that may be gen-

erated by outside doors, windows, air vents, air conditioning units, extractor

fans, ceiling fans etc. See section 4.1 for more information on ventilation.

Clearances to non-combustible materials

Non combustible surfaces are defined as brick, metal, natural stone, concrete

etc. and also a number of man-made materials impervious to flame. If in doubt

refer to the material manufacturer for further information before proceeding

with installation.

Clearances to the sides of the appliance are 100mm (4”). Clearance to the

front of the appliance is 500mm (20”). 

The back of the appliance may be installed directly in front of a non-com-

bustible wall, providing the area behind the appliance is flat and does not inter-

fere with the various vent holes in the back panel of the appliance. 

3.1 ROOM SIZING

4.0 SITE REQUIREMENTS

Specifications

NG Models

LPG Models

Main burner injector

Stereo size 1.30

Stereo size 83

Oxypilot 

SIT 9110/ Copreci 21100 2F/CHMU13125A   

TBC

Gas Control

Teddington TESA 3173/011

Teddington TESA 3173/011

Gas Inlet 

8mm restrictor elbow

8mm restrictor elbow

Ignition

Battery Spark

Battery Spark

Spark Gap

3.5 - 4.5mm

3.5 - 4.5mm

3.0 INSTALLATION REQUIREMENTS

Figure 2

© 2014 Focal Point Fires plc.

Summary of Contents for DALVIK

Page 1: ...ritten per mission of Focal Point Fires plc 1 Revision B 11 14 GB IE INTHE UK ALWAYS USE A GAS SAFE REGISTERED ENGINEERTO INSTALL REPAIR OR SERVICETHIS APPLIANCE MODEL SHOWN DALVIK FLUELESS STOVE LEIR...

Page 2: ...form of background heating present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the room On first light up of a new appliance bur...

Page 3: ...e in cubic feet ft3 by 35 3 This appliance may be installed in any room in the home except bathrooms In accordance with BS5871 part 4 installation in bedrooms is permitted If the appliance is to be in...

Page 4: ...ends on the depth or protrusion from the wall of the TV but must extend at least 50mm outward from the front of the TV See figure 5 If a minimum distance of 50mm to the TV from the shelf front cannot...

Page 5: ...UNPACKING THE APPLIANCE Remove the outer packaging remove any instructions Read ALL these instructions before continuing to unpack or install this appliance Lift off the remaining packaging components...

Page 6: ...ront casting using the M6 x 15mm screw supplied 9 To re assemble the castings read instructions in reverse order 10 Attach the control handle to the burner assembly through the opening in the front pa...

Page 7: ...t be lit manually Figure 17 Spark gap Turn on and test the gas supply up to the fire for any leaks in accordance with the current edition of BS 6891 natural gas installations or the current edition of...

Page 8: ...section 2 0 of these instructions The fire is factory set to achieve the correct flow rates at the specified inlet pressure Any significant variation in the operating pressure could indicate a supply...

Page 9: ...val Ensure setting pressures are as stated in Section 2 Appliance Data It is recommended that the catalysts are inspected for signs of damage and dirt during routine servicing procedures The expected...

Page 10: ...aft Fire is too close to an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly Pilot lig...

Page 11: ...servicing section for further reference The guard glass front is to prevent the risk of fire or injury from burns and no part of it should be permanently removed It Does Not Give Full Protection ForYo...

Page 12: ...d be properly de commissioned and sealed at the base using non com bustible materials The old flue should be ventilated to prevent condensation and possible damage to the fabric of the building This v...

Page 13: ...or can be moveable and can be used with open fires including combination grates or closed fires including room heaters and stoves See figures 6 7 for fireguard examples The fireguards specified are n...

Page 14: ...is visible behind the centre of the burner Move the control handle fully right to the SPARK position and hold there for approximately ten seconds Now release the control han dle and the pilot should s...

Page 15: ...reate dust from the logs Where neces sary replace damaged components with genuine spares Seal scrap components in plastic bags and dispose of at proper refuse sites as directed 10 0 REPLACING THE BATT...

Page 16: ...GAS SAFE registration No Model Fire serial No Supplied by Name contact details of installer 13 0 SERVICE HISTORY Date of service Serviced by name Contact details of Engineer GAS SAFE No Date installed...

Page 17: ...ide together with the registration number 3 Your appliance must have been serviced annually by Gas Safe registered installer evidence of which must be provided such as the receipt 4 Purchase s must be...

Reviews: